b1-14: Phase Order Selection
No.
Name
(Hex.)
b1-14
Phase Order Selection
(01C3)
0 : Standard
1 : Phase Order Switch
b1-15: Freq. Ref. Sel. 2
No.
Name
(Hex.)
b1-15
Freq. Ref. Sel. 2
(01C4)
This parameter is enabled when H1-xx = 9 [MFDI Function Select = Ext Ref 1/2] is activated.
Note:
• Push
on the keypad to set the input mode to LOCAL and use the keypad to enter the frequency reference.
• If the frequency reference is 0 Hz or less than or equal to the value set in E1-09 [Min Output Frequency] and the drive receives the Run
command, the RUN LED on the keypad will flash. Examine the setting for the frequency reference input and enter a value more than
or equal to E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals AI1 and AI2 to input an analog frequency reference with a voltage or current input signal.
• Voltage Input
Refer to
Table 12.8
to use a voltage signal input to one of the MFAI terminals.
Terminal Signal
Terminal
Level
AI1
0 - 10 V (Lower Limit
at 0)
0 - 10 V (Without
Lower Limit)
AI2
0 - 10 V (Lower Limit
at 0)
0 - 10 V (Without
Lower Limit)
Figure 12.17 Example of Setting the Frequency Reference with a Voltage Signal to Terminal AI1
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for frequency reference 2.
Table 12.8 Frequency Reference Voltage Input
Parameter Settings
Signal Level
Function Selection
Selection
H3-01 = 0
H3-02 = 4
[Freq Ref/BIAS]
H3-01 = 1
H3-01 = 0
H3-10 = 4
[Freq Ref/BIAS]
H3-01 = 1
Description
Description
Gain
Bias
H3-03
H3-04
H3-11
H3-12
12.2 b: APPLICATION
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 4)
Note
-
Set DIP switch S1 to "V" for
voltage input.
451
12