Setting Value
Function
1D
RunCmdSource
1E
Motor2 Select
1F
Restart Enable
20
FltReset Active
21
PolePos Detection
22
Ext 24V Supply
2F
@SpeedSearch
30
During Torque Limit
32
TrqDetect1NO
33
TrqDetect1NC
37
TrqDetect2NO
38
TrqDetect2NC
39
Timer Output
3C
Comparator 1
3D
Comparator 2
3E
PID Fbk Low
3F
PID Fbk High
4A
DC Bus Undervolt
4B
FreqRef Loss
4C
BrkRes Fault
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the selected Run command source.
ON : The keypad is the Run command source.
OFF : Parameter b1-02 or b1-16 [Run Comm. Sel 1 or Run Comm. Sel 2] is the Run command source.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the Auto Restart function is trying to restart after a fault.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal turns on when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position
of the PM motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when there is an external 24V power supply between terminals E24V-A0V.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive is doing speed search.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the torque reference is the torque limit set with L7 parameters or H3-02 or H3-10
[MFAI Function Select].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with L6-02 [Trq Det1 Level], or the level is less
than the torque value set with L6-02 for longer than the time set with L6-03 [Trq Det1 Time].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-02 [Trq Det1 Level], or the level is less
than the torque value set with L6-02 for longer than the time set with L6-03 [Trq Det1 Time].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque is more than the torque value set with L6-05 [Trq Det2 Level], or the level is less
than the torque value set with L6-05 for longer than the time set with L6-06 [Trq Det2 Time].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque is more than the torque value set with L6-05 [Torque Detection Level 2], or the
level is less than the torque value set with L6-05 [Torque Detection Level 2] for longer than the time set with L6-06
[Torque Detection Time 2].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use this setting when the drive uses the timer function as an output terminal.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates if the monitor value set with H2-20 [Compare1 Mon.Selection] is in range of the values of
H2-21 [Compare1 Low Limit] and H2-22 [Compare1 Up Limit] for the time set in H2-24 [Compare1 On-Delay
Time].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates if the monitor value set with H2-26 [Compare2 Mon.Selection] is not in the range of the
values of H2-27 [Compare2 Low Limit] and H2-28 [Compare2 Up Limit] for the time set in H2-30 [Compare2
On-Delay Time].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects FbL [PID Feedback Loss].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects FbH [Excessive PID Feedback].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with
L2-05 [UV Detection Lvl (Uv1)]. The terminal also turns on when there is a fault with the DC bus voltage.
ON : The DC bus voltage is less than the setting value of L2-05.
OFF : The DC bus voltage is more than the setting value of L2-05.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects a loss of frequency reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor
fault.
Description
11.9 H: TERMINALS
Ref.
603
603
603
603
603
603
603
604
604
604
604
604
605
605
605
606
606
606
606
606