Omron Q2V Series Technical Manual page 609

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

Example
Analog Input
Terminal AI1 Setting
Settings
Frequency
H3-02 = 1 [AI1 Function
Reference When
Selection= AuxFreqRef1]
You Adjust the
H3-03 = 200.0 [AI1 Gain Setting =
Gain Setting
200%]
H3-04 = 0.0 [AI1 Bias Setting =
0.0%]
Frequency
H3-02 = 1 [AuxFreqRef1]
Reference When
H3-03 = 100.0 [100.0%]
You Set the Bias
H3-04 = -25.0 [-25.0%]
to a Negative
Number
Modbus Multi-Function AI1 to 3 Function Selection
You can set the MFAI function to Modbus register15C1 to 15C3 (Hex.) [Mbus Reg 15C1h through 15C3h Input
Function]. Use H3-40 to H3-42 [15C1h Input Function to 15C3h Input Function] to set the function and use H3-
43 [Mbus In FilterTime Const] to set the input filter.
Register No.
(Hex.)
15C1
15C2
15C3
*1
Set as 100% = 4096.
Figure 12.90 Functional Block Diagram for Modbus Multi-Function AI Command 1
SIEPCYEUOQ2V01A Q2V Technical Manual
When you input a 10 V signal, the frequency reference will be 200%.
When you input a 5 V signal, the frequency reference will be 100%.
When you input a 5 V or more signal, E1-04 [Max Output Frequency] will limit the drive output and the frequency
reference will be 100%.
When you input a 0 V signal, the frequency reference will be -25%.
When H3-01 = 0 [AI1 Signal Level Select = 0 to 10V (Lower Limit at 0)]
– When you input a 0 V to 2 V signal, the frequency reference will be 0%.
– When you input a 2 V to 10 V signal, the frequency reference will be 0% to 100%.
When H3-01 = 1 [0 to +10 V (Without Lower Limit)]
– When you input a 0 V to 2 V signal, it enables signals of positive and negative polarities and the motor
rotates in reverse.
Table 12.48 Modbus Multi-Function AI Command Register
Name
Mbus Reg 15C1h Input Function
Mbus Reg 15C2h Input Function
Mbus Reg 15C3h Input Function
12.7 H: TERMINALS
Frequency Reference
Range
*1
-32767 - +32767
-32767 - +32767
-32767 - +32767
Parameter
H3-40
H3-41
H3-42
12
609