Omron Q2V Series Technical Manual page 563

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

F7-22: E/IP Time Scale Factor
No.
Name
(Hex.)
F7-22
E/IP Time Scale Factor
(03FA)
F7-23 to F7-32: DynOut.Ass116 P1 to 10 for CommCard
No.
Name
(Hex.)
F7-23 - F7-27
DynOut.Ass116 P1 to 10
for CommCard
(03FB - 03FF)
F7-28- F7-32
(0370 - 0374)
F7-33 to F7-42: DynIn.Ass166 P1 to 10 for CommCard
No.
Name
(Hex.)
F7-33 - F7-42
DynIn.Ass166 P1 to 10 for
CommCard
(0375 - 037E)
F7-60: PZD1 WR(CtrlWrd)
No.
Name
(Hex.)
F7-60
PZD1 WR(CtrlWrd)
(0780)
F7-61: PZD2 WR(FRef)
No.
Name
(Hex.)
F7-61
PZD2 WR(FRef)
(0781)
F7-62: PZD3 Write
No.
Name
(Hex.)
F7-62
PZD3 Write
(0782)
F7-63: PZD4 Write
No.
Name
(Hex.)
F7-63
PZD4 Write
(0783)
F7-64: PZD5 Write
No.
Name
(Hex.)
F7-64
PZD5 Write
(0784)
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets Output Assembly 116. The drive writes the values from Output Assembly 116 to the Modbus
address register that is stored for each parameter. The drive will not write the values from Output
Assembly 116 to the registers when the Modbus address is 0.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets Input Assembly 166. The drive sends the values from the Modbus address registers stored for
each parameter to Input Assembly 166. The drive returns the default register value for the option
card when the Modbus address is 0 and the value sent to Input Assembly 166 is not defined.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Modbus address for PZD1 (PPO output). PZD1 (PPO output) functions as the STW when
F7-60 = 0, 1, or 2.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the Modbus address for PZD2 (PPO output). PZD2 (PPO output) functions as the HSW when
F7-61 = 0, 1, or 2.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Modbus address for PZD3 (PPO output). A value of 0, 1, or 2 will disable the PZD3
(PPO output) write operation to the Modbus register.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Modbus address for PZD4 (PPO output). A value of 0, 1, or 2 will disable the PZD4
(PPO output) write operation to the Modbus register.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Modbus address for PZD5 (PPO output). A value of 0, 1, or 2 will disable the PZD5
(PPO output) write operation to the Modbus register.
Description
Description
Description
Description
Description
Description
Description
Description
12.6 F: OPTIONS
Default
(Range)
0
(-15 - +15)
Default
(Range)
0
Default
(Range)
0
Default
(Range)
0
Default
(Range)
0
Default
(Range)
0
Default
(Range)
0
Default
(Range)
0
12
563