E3-01: M2 Control Method Selection
No.
Name
(Hex.)
E3-01
M2 Control Method
Selection
(0319)
Note:
• When you change this setting, the drive will set all parameters that are dependent on E3-01 to their default settings.
• Parameter L1-01 [Motor Cool Type for OL1 Calc] sets the protection operation of oL1 [Motor Overload] the same as Motor 1.
• When you use parameter A1-03 [Init Parameters] to initialize the drive, this parameter is not reset.
0 : V/f Control
2 : OLVector
E3-04: M2 Max Out Frequency
No.
Name
(Hex.)
E3-04
M2 Max Out Frequency
(031A)
E3-05: M2 Max Out Voltage
No.
Name
(Hex.)
E3-05
M2 Max Out Voltage
(031B)
E3-06: M2 Base Frequency
No.
Name
(Hex.)
E3-06
M2 Base Frequency
(031C)
E3-07: M2 Mid A Frequency
No.
Name
(Hex.)
E3-07
M2 Mid A Frequency
(031D)
E3-08: M2 Mid A Voltage
No.
Name
(Hex.)
E3-08
M2 Mid A Voltage
(031E)
E3-09: M2 Min Out Frequency
No.
Name
(Hex.)
E3-09
M2 Min Out Frequency
(031F)
E3-10: M2 Min Out Voltage
No.
Name
(Hex.)
E3-10
M2 Min Out Voltage
(0320)
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the control method for motor 2.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Set the maximum output frequency for the motor 2 V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the maximum output voltage for the motor 2 V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the base frequency for the motor 2 V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a middle output frequency for the motor 2 V/f pattern.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets a middle output voltage for the motor 2 V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the minimum output frequency for the motor 2 V/f pattern.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the minimum output voltage for the motor 2 V/f pattern.
Description
Description
Description
Description
Description
Description
Description
Description
12.5 E: MOTOR
Default
(Range)
0
(0, 2)
Default
(Range)
Determined by E3-01
(40.0 - 590.0 Hz)
Default
(Range)
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Default
(Range)
Determined by E3-01
(0.0 - E3-04)
Default
(Range)
Determined by E3-01
(0.0 - E3-04)
Default
(Range)
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Default
(Range)
Determined by E3-01
(0.0 - E3-04)
Default
(Range)
Determined by E3-01
12
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)