Model Specifications (Single-Phase 200 V Class) - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

10.4

Model Specifications (Single-Phase 200 V Class)

Model
Maximum Applicable Motor
Output (kW)
Maximum Applicable Motor
Output (HP)
Rated Input
Input
Current (A)
Rated Output
Capacity (kVA)
*3
Rated Output
Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage
Maximum Output Frequency
Measures for
AC reactor
Harmonics
Braking Device Braking Transistor
EMC Filter
EMC Filter
IEC61800-3
Rated Voltage/Rated Frequency
Permitted Voltage Fluctuation
Power Supply
Permitted Frequency Fluctuation
Input Power
(kVA)
*1
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*3
The rated output capacity is calculated with a rated output voltage of 220 V.
SIEPCYEUOQ2V01A Q2V Technical Manual
Table 10.5 Ratings (Single-Phase 200 V Class)
B001
B002
*1
HD
0.1
0.25
0.2
*2
ND
0.37
0.18
*1
HD
1/6
1/4
*2
ND
1/6
1/4
HD
1.4
2.8
ND
2.0
5.0
HD
0.3
0.6
ND
0.5
0.7
HD
0.8
1.6
ND
1.2
1.9
• HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10 minutes.
• ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is once every 10 minutes.
Note:
Derating may be necessary for applications that start and stop frequently.
HD: 10 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Single-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
• V/f Control, OLVector, PM OLVector: 590 Hz
• PM AOLVector: 270 Hz
• EZ Vector: 120 Hz
External options
Standard internal characteristics
Category C1 (Conducted emission)
• Single-phase AC power supply 200 V to 240 V at 50/60 Hz 
• DC power supply 270 V to 340 V
-15% to +10%
±5%
HD
0.4
0.7
ND
0.5
1.3

10.4 Model Specifications (Single-Phase 200 V Class)

B004
B006
0.55
1.1
0.75
1.1
1/2
1
3/4
1.5
5.5
11
7.3
13.8
1.1
1.9
1.3
2.3
3
5
3.5
6
1.5
2.9
1.9
3.6
B010
B012
1.5
2.2
2.2
3.0
2
3
3
3
14.1
20.6
20.2
24.0
3
4.2
3.7
4.6
8
11
9.6
12.2
HD: 8 kHz without derating the drive capacity.
ND: 2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz
maximum.
External
External
3.7
5.4
5.3
6.3
B018
4.0
-
5
-
35.0
-
6.7
-
17.6
-
options
options
9.2
-
10
295

Advertisement

Table of Contents
loading