Control Circuit Terminal Block Functions - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

*2
Install the wire jumpers between terminals DIC-D24V and DIC-D0V to set the MFDI power supply (sinking/sourcing mode or
internal/external power supply).
NOTICE: Do not close the circuit between terminals D24V and D0V. A closed circuit between these terminals will cause
damage to the drive.
• Sinking Mode: Install a jumper between terminals DIC and D24V.
NOTICE: Do not close the circuit between terminals DIC and D0V. A closed circuit between these terminals will cause
damage to the drive.
• Sourcing Mode: Install a jumper between terminals DIC and D0V.
NOTICE: Do not close the circuit between terminals DIC and D24V. A closed circuit between these terminals will cause
damage to the drive.
• External Power Supply: No jumper is necessary between terminals DIC-D0V and terminals DIC-D24V.
*3
The maximum output current capacity for terminal +10V on the control circuit is 20 mA.
NOTICE: Damage to Equipment. Do not install a jumper between terminals +10V and A0V. A closed circuit between these
terminals will cause damage to the drive.
*4
DIP switch S1 sets terminal AI2 for voltage or current input. The default setting for S1 is current input ("I" side).
*5
Do not ground the control circuit terminals A0V or connect them to the drive.
NOTICE: Do not ground the AC control circuit terminals and only connect the A0V terminals according to the product
instructions. If you connect the AC terminals incorrectly, it can cause damage to the drive.
*6
Do not connect terminals D24V and A0V inversely. Failure to obey will cause damage to the drive.
*7
Set DIP switch S2 to the ON position to enable the termination resistor in the last drive when you use Modbus communications.
*8
To use the internal power supply with the Safe Disable input, use sourcing mode.
*9
Disconnect the wire jumpers between H1 and HC and H2 and HC to use the Safe Disable input.
*10 Use multi-function analog monitor outputs with analog frequency meters, ammeters, voltmeters, and wattmeters. Do not use monitor
outputs with feedback-type signal devices.
*11 Jumper S5 sets terminal AO for voltage or current output. The default setting for S5 is voltage output ("V" side).

Control Circuit Terminal Block Functions

Hx-xx parameters set functions for the multi-function input and output terminals.
WARNING! Sudden Movement Hazard. Correctly wire and test all control circuits to make sure that the control circuits operate
correctly. If you use a drive that has incorrect control circuit wiring or operation, it can cause death or serious injury.
NOTICE: The drive can fail if users frequently turn the drive ON and OFF with the MC on the power source side to Run and
Stop the drive. Incorrect operation can decrease the service life of the relay contacts and electrolytic capacitors. If you
frequently use the magnetic contactor on the power source side to Run and Stop the drive, it can cause drive failure.
Multi-function Input Terminals
This chapter contains a list of input terminals and functions.
Terminal
Name (Default)
MFDI selection 1
DI1
(ON: Forward run OFF: Stop)
MFDI selection 2
DI2
(ON: Reverse run OFF: Stop)
MFDI selection 3
DI3
(External fault (N.O.))
MFDI selection 4
DI4
(Fault reset)
MFDI selection 5
DI5
(Multi-step speed reference 1)
MFDI selection 6
DI6
(Multi-step speed reference 2)
MFDI selection 7
DI7
(Jog command)
D0V
MFDI power supply 0 V
DIC
MFDI selection common
D24V
MFDI power supply +24 Vdc
SIEPCYEUOQ2V01A Q2V Technical Manual
Table 3.5 Digital Inputs
Photocoupler
24 V, 6 mA
Note:
To set the MFDI power supply (Sinking/Sourcing Mode or internal/external power supply), install wire
jumpers between terminals DIC-D24V and DIC-D0V.
• Sinking Mode: Install a jumper between terminals DIC and D24V.
NOTICE: Do not close the circuit between terminals DIC and D0V. A
closed circuit between these terminals will cause damage to the drive.
• Sourcing Mode: Install a jumper between terminals DIC and D0V.
NOTICE: Do not close the circuit between terminals DIC and D24V. A
closed circuit between these terminals will cause damage to the drive.
• External Power Supply: No jumper is necessary between terminals DIC-D0V and terminals DIC-
D24V.
MFDI power supply, 24 V (maximum 150 mA)
NOTICE: Do not close the circuit between terminals D24V and D0V. A
closed circuit between these terminals will cause damage to the drive.
3.5 Control Circuit Wiring
Function (Signal Level)
3
75