Ground the wire shielding on the drive side and motor side.
A - Drive
B - 10 m (32.8 ft) maximum
C - Motor
Note:
• Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
• Keep the wire as short as possible. The maximum wiring length between the drive and motor is:
–2xxxA, BxxxA, 4xxxA: 10 m (32.8 ft)
• Keep the grounding wire as short as possible.
4.
Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications or local safety standards.
A - Braided shield cable
B - Metal plate
SIEPCYEUOQ2V01A Q2V Technical Manual
D - Metal conduit
E - Grounding wire
Figure 5.11 Wiring the Drive and Motor
C - Cable clamp (conductive)
Figure 5.12 Ground the shield