Omron Q2V Series Technical Manual page 452

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

12.2 b: APPLICATION
Note:
You can also use this diagram to wire terminal AI2.
• Current Input
Refer to
Table 12.9
to use a current signal input to one of the MFAI terminals.
Terminal
Signal Level
AI2
4 - 20 mA
0 - 20 mA
Figure 12.18 Example of Setting the Frequency Reference with a Current Signal to Terminal AI2
Changing between Master and Auxiliary Frequency References
Use the multi-step speed reference function to change the frequency reference input between terminals AI1 and
AI2.
2 : Modbus
Use Modbus communications to enter the frequency reference.
3 : Option PCB
Use a communications option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If you set b1-15 = 3 but you do not connect an option card, oPE03 [Multi-Function Input Setting Err] will flash on the keypad.
4 : Pulse Train Input
Use a pulse train signal from the pulse train input terminal PI to enter the frequency reference.
Do this procedure to make sure that the pulse train signal is operating correctly.
1. Set b1-15 = 4, H6-01 = 0 [PI Pulse Train Function = Freq Ref].
2. Set H6-02 [PI Frequency Scale] to the number of pulses that determine 100% of the frequency reference.
3. The terminal set in H1-xx = 9 [MFDI Function Select = Ext Ref 1/2] is activated.
4. Enter a pulse train signal on the terminal PI and make sure that the keypad shows a correct frequency
reference.
b1-16: Run Comm. Sel 2
No.
Name
(Hex.)
b1-16
Run Comm. Sel 2
(01C5)
Activate H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection] to enable this parameter.
0 : Keypad
Use the keypad to enter the Run command.
You can use the JOG operation or the FWD/REV commands from the keypad.
452
Table 12.9 Frequency Reference Current Input
Signal Level
Function Selection
Selection
H3-09 = 2
H3-10 = 4
[Freq Ref/BIAS]
H3-09 = 3
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the input method for Run Command 2 when the user switches the control circuit terminals
ON/OFF to change the Run command source.
Parameter Settings
Gain
H3-11
Description
SIEPCYEUOQ2V01A Q2V Technical Manual
Note
Bias
H3-12
Set DIP switch S1 to
"I" for current input.
Default
(Range)
0
(0 - 3)