Omron Q2V Series Technical Manual page 21

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

No.
3
A: IP20 protection Class
4
Input power supply voltage
• B: Single-Phase AC 200 V Class
• 2: Three-Phase AC 200 V Class
• 4: Three-Phase AC 400 V Class
5
Rated output current
Note:
Refer to the rated output current list for more information.
6
EMC noise filter
• A: Built-in EMC filter
• B: Without built-in EMC filter
7
Coating Specification
• A: Standard
8
Version
Rated Output Current
These output current values are applicable for drives that operate at standard specifications.
• These output current values are applicable for drives that operate at standard specifications.
• Derate the current in applications that:
– Increase the carrier frequency
– Have high ambient temperature
– Install drives side-by-side.
• Use C6-01 [ND/HD Duty Selection] to select Normal Duty rating (ND) or Heavy Duty rating (HD).
Model
Maximum Applicable Motor
2001
2002
2004
2006
2008
2010
2012
2018
2021
2030
2042
2056
2070
2082
SIEPCYEUOQ2V01A Q2V Technical Manual
Table 1.2 Three-Phase AC 200 V Class
HD Rating
[C6-01 = 0]
(Default)
Rated output current
Output
A
kW
0.1
0.8
0.25
1.6
0.55
3.0
1.1
5.0
1.1
6.9
1.5
8.0
2.2
11.0
3.0
17.6
4.0
17.6
5.5
25.0
7.5
33.0
11.0
47.0
15.0
60.0
18.5
75.0
1.1 Model Number and Nameplate Check
Description
Maximum Applicable Motor
Output
kW (HP)
0.18
0.37
0.75
1.1
1.5
2.2
3.0
3.7
5.5
7.5
11.0
15.0
18.5
22.0
ND Rating
[C6-01 = 1]
Rated output current
A
1.2
1.9
3.5
6.0
8.0
9.6
12.2
17.5
21.0
30.0
42.0
56.0
70.0
82.0