Omron Q2V Series Technical Manual page 719

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

T2-05: PMMot Rated Voltage
No.
Name
(Hex.)
T2-05
PMMot Rated Voltage
(0732)
T2-06: PMMot Rated Current
No.
Name
(Hex.)
T2-06
PMMot Rated Current
(0733)
T2-07: PMMot Base Frequency
No.
Name
(Hex.)
T2-07
PMMot Base Frequency
(0753)
T2-08: PMMot Poles Number
No.
Name
(Hex.)
T2-08
PMMot Poles Number
(0734)
T2-09: PMMot Base Speed
No.
Name
(Hex.)
T2-09
PMMot Base Speed
(0731)
T2-10: PMMot Stator Resistance
No.
Name
(Hex.)
T2-10
PMMot Stator Resistance
(0754)
Note:
This parameter does not set line-to-line resistance.
T2-11: PMMot dAxis Inductance
No.
Name
(Hex.)
T2-11
PMMot dAxis Inductance
(0735)
T2-12: PMMot qAxis Inductance
No.
Name
(Hex.)
T2-12
PMMot qAxis Inductance
(0736)
T2-13: KE Unit Selection
No.
Name
(Hex.)
T2-13
KE Unit Selection
(0755)
SIEPCYEUOQ2V01A Q2V Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the rated voltage (V) of the motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the rated current (A) of the motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the base frequency (Hz) of the motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the number of motor poles.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the motor base speed (min
-1
(r/min)).
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the stator resistance for each motor phase.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the d-axis inductance of the motor on a per phase basis.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the q-Axis inductance of the motor on a per phase basis.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the units that the drive uses to set the induced voltage constant.
Description
Description
Description
Description
Description
Description
Description
Description
Description
12.11 T: AUTOTUNING
Default
(Range)
200 V Class: 200.0 V, 400
V: 400.0 V
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Default
(Range)
Determined by o2-04
(10% to 200% of the drive
rated current)
Default
(Range)
87.5 Hz
(0.0 - 590.0 Hz)
Default
(Range)
6
(2 - 48)
Default
(Range)
1750 min
-1
(r/min)
(0 - 34500 min
-1
(r/min))
Default
(Range)
Determined by T2-02
(0.000 - 65.000 Ω)
Default
(Range)
Determined by T2-02
(0.00 - 600.00 mH)
Default
(Range)
Determined by T2-02
(0.00 - 600.00 mH)
Default
(Range)
1
(0, 1)
719
12

Advertisement

Table of Contents
loading

Table of Contents