12.2 b: APPLICATION
• U5-04 [PID Setpoint]
• U5-99 [PID Setpoint Command]
0 : No Decimal Places
1 : 1 Decimal Place
2 : 2 decimal places
3 : 3 Decimal Places
b5-40: Fref Mon@PID
No.
Name
(Hex.)
b5-40
Fref Mon@PID
(017F)
0 : U1-01 with PID Output
Monitor U1-01 shows the frequency reference that was increased or decreased by the PID output.
1 : U1-01 without PID Output
Monitor U1-01 shows the actual frequency reference.
b5-47: PID Out Rev Operation Mode
No.
Name
(Hex.)
b5-47
PID Out Rev Operation
Mode
(017D)
This parameter is enabled when b5-01 = 1 [PID Enable = Enabled].
0 : Lower Limit is Zero
When PID output is negative, PID output is limited to 0 and drive output is shut off.
1 : Negative Output Accepted
When the PID output is negative, the motor will rotate in reverse.
b5-53: PID I Ramp Limit
No.
Name
(Hex.)
b5-53
PID I Ramp Limit
(0B8F)
RUN
Note:
• This parameter is disabled when set to 0.0 Hz.
• When b5-53 > 0.0 Hz and the drive enables the integrator ramp limit, the PID integrator value limit is the range set by the output
frequency ± b5-53.
• When the PID feedback changes quickly, gradually decrease the this parameter in 0.1 Hz increments to decrease the speed of the
response of PID control.
b5-54: PID Softstarter Selection
No.
Name
(Hex.)
b5-54
PID Softstarter Selection
(0BB7)
Table 12.16
shows how the soft-starter responds to PID input/output.
Selection
Soft Starter 1
Soft Starter 2
0 : Disab PID Softstart
478
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the contents for monitor U1-01 [Frequency Reference] in PID control.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets reverse motor rotation when the PID control output is negative.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the responsiveness of PID control when the PID feedback changes quickly.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets how the soft-starter responds to PID input/output.
Table 12.16 Soft Starter and PID Input/Output
PID Frequency Reference
PID Frequency Reference
Input
Frequency Reference
Soft Starter Output
Description
Description
Description
Description
Soft Starter Input
Output
Soft Starter Input
PID Frequency Reference Output
Output Frequency
Frequency Reference
Default
(Range)
0
(0, 1)
Default
(Range)
1
(0, 1)
Default
(Range)
0.0 Hz
(0.0 - 10.0 Hz)
Default
(Range)
0
(0, 1)
Soft Starter Output
Output Frequency
PID Frequency Reference Input