3.4 Main Circuit Terminal Block Wiring Procedure - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

3.4 Main Circuit Terminal Block Wiring Procedure

A - Cable clamp
Screw
Screw Shape
Size
M3
M4
*1
M5
M6
(WAF: 5 mm)
*1
When you wire drive models 2042, 2056, 4031, 4038, 4044, and 4060, select the correct tools for the wire gauge.
*2
Use 6.35 mm (0.25 in) bit socket holder.
*3
Use a torque wrench that can apply this torque measurement range.
Main Circuit Terminal Block Wiring Procedure
When terminals R/L1, S/L2, T/L3, -, +1, and +2 have IP20 protection covers, remove them.
1.
Put a wire with prepared ends into the main circuit terminal block.
Look through the opening in the drive case to make sure that you correctly installed the wires into the
terminal block.
Note:
There is a jumper between terminals +1 and +2. Remove the jumper, then wire to terminals +1 and +2.
72
Figure 3.17 Strain Relief Example
Table 3.4 Recommended Wiring Tools
Wire Gauge
Adapter
-
Bit
-
Bit
≤ 25 mm
2
(AWG 10)
Bit
≥ 30 mm
2
(AWG 8)
-
Bit
Figure 3.18 Install the Electrical Wire
Bit Model
Torque Driver Model
(Manufacturer)
(Tightening Torque)
TSD-M 1,2NM
SF-BIT-SL 0,5X3,0-70
(0.3 - 1.2 N∙m
(PHOENIX CONTACT)
(2.7 - 10.6 in∙lb))
TSD-M 3NM
SF-BIT-SL 1,0X4,0-70
(1.2 - 3.0 N∙m
(PHOENIX CONTACT)
(10.6 - 26.6 in∙lb))
TSD-M 3NM
(1.2 - 3.0 N∙m
SF-BIT-SL 1,2X6,5-70
(10.6 - 26.6 in∙lb))
(PHOENIX CONTACT)
SF-BIT-HEX 5-50
(PHOENIX CONTACT)
Torque Wrench
(Tightening Torque)
-
-
-
4.1 - 4.5 N∙m
-
(36.3 - 39.8 in∙lb)
5 - 9 N∙m
-
(44.3 - 79.7 in∙lb)
SIEPCYEUOQ2V01A Q2V Technical Manual