12.7 H: TERMINALS
12: AI Input Sel
Setting Value
Function
12
AI Input Sel
ON : Terminal selected with H3-14 is enabled
OFF : Terminal selected with H3-14 is disabled
15: FWD/REV Det
Setting Value
Function
15
FWD/REV Det
ON : Reverse run
The drive knows that the motor is rotating in the reverse direction.
OFF : Forward run
The drive knows that the motor is rotating in the forward direction.
16: Ref Sample
Setting Value
Function
16
Ref Sample
When the terminal is active for 100 ms, this function reads a sample of the analog frequency reference and holds
that sample. When you input the sample/hold command again, the function again reads a sample of the analog
frequency reference and holds that sample. When you turn off the power, the drive erases the saved analog
frequency and resets the frequency reference to 0.
Figure 12.68
shows an example of how the function operates.
You cannot set the Reference Sample Hold function at the same time as these functions:
• H1-xx = 17 [Ac/Dec Hold]
• H1-xx = 62, 63 [Up Command, Down Command]
• H1-xx = E to 10 [Offset Frq 1 to Offset Frq 3]
• H1-xx = 65, 66 [Up2 Command, Dw2 Command]
If you set them at the same time, the drive will detect oPE03 [Multi-Function Input Setting Err].
17: Ac/Dec Hold
Setting Value
Function
17
Ac/Dec Hold
If the terminal is deactivated, the drive restarts acceleration and deceleration.
When the acceleration/deceleration ramp hold terminal is activated and d4-01 = 1 [FRef Hold Selection =
Enabled], the drive will store the output frequency in memory. While the acceleration/deceleration ramp hold
command is activated, the drive will always restart the motor at this output frequency.
574
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the command that enables or disables the terminals selected in H3-14 [An.In Term.Enable Sel].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Set the motor rotation direction when you use Simple Closed Loop V/f Control method.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to sample the frequency reference at terminal AI1 or AI2, and hold the frequency reference at that frequency.
Figure 12.68 Reference Sample Hold
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
Description
Description
Description
Description
SIEPCYEUOQ2V01A Q2V Technical Manual