Omron Q2V Series Technical Manual page 343

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

No.
Name
(Hex.)
F6-30
PROFI-DP Address
(03CB)
F6-31
PROFI-DP Clear
Command Mode
(03CC)
F6-32
PROFI-DP Data Format
Select
(03CD)
F6-35
CANopen Address
(03D0)
F6-36
CANopen BaudRate
(03D1)
F6-50
DNet MAC Address
(03C1)
F6-51
DNet Baud Rate
(03C2)
F6-52
DNet PCA Setting
(03C3)
F6-53
DNet PPA Setting
(03C4)
F6-54
DNet Idle Fault
Detection
(03C5)
SIEPCYEUOQ2V01A Q2V Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the node address for PROFIBUS-DP communication. Restart the drive after you
change the parameter setting.
Note:
Be sure to set an address that is different than all other node addresses. Do not set
this parameter to 0.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets what the drive will do after it receives the Clear Mode command.
0 : Reset
1 : Hold Previous State
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the data format of PROFIBUS-DP communication. Restart the drive after you
change the parameter setting.
0 : PPO Type
1 : Conventional
2 : PPO (bit0)
3 : PPO (Enter)
4 : Conv (Enter)
5 : PPO (bit0,Enter)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the node address for CANopen communication. Restart the drive after you change
the parameter setting.
Note:
Be sure to set an address that is different than all other node addresses. Do not set
this parameter to 0. Incorrect parameter settings will cause AEr [Station Address
Setting Error] errors and the L.ERR LED on the option will come on.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the CANopen communications speed. Restart the drive after you change the
parameter setting.
0 : Auto-Detection
1 : 10 kbps
2 : 20 kbps
3 : 50 kbps
4 : 125 kbps
5 : 250 kbps
6 : 500 kbps
7 : 800 kbps
8 : 1 Mbps
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the MAC address for DeviceNet communication. Restart the drive after you change
the parameter setting.
Note:
Be sure to set a MAC address that is different than all other node addresses. Do not
set this parameter to 0. Incorrect parameter settings will cause AEr [Station Address
Setting Error] errors and the MS LED on the option will flash.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DeviceNet communications speed. Restart the drive after you change the
parameter setting.
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
3 : Adjustable from Network
4 : Detect Automatically
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the format of data that the DeviceNet communication master sends to the drive.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the format of data that the drive sends to the DeviceNet communication master.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to detect EF0 [Option Card External Fault] when the drive does not
receive data from the DeviceNet master.
0 : Enabled
1 : Disabled, No Fault Detection
2 : Vendor Specific
3 : RUN Forward
4 : RUN Reverse
11.8 F: OPTIONS
Default
Ref.
(Range)
0
555
(0 - 125)
0
556
(0, 1)
0
556
(0 - 5)
0
556
(0 - 126)
0
556
(0 - 8)
0
557
(0 - 64)
0
557
(0 - 4)
21
557
(0 - 255)
71
557
(0 - 255)
0
557
(0 - 4)
343