Parameters That Change From The Default Settings With E3-01; Method Selection]; Parameters That Change From The Default Settings With E3-01 [M2 Control Method Selection] - Omron Q2V Series Technical Manual

Driving quality, 200 v class, three-phase: 0.1 to 22 kw, 200 v class, single-phase: 0.1 to 4.0 kw, 400 v class, three-phase: 0.37 to 30 kw
Table of Contents

Advertisement

11.18 Parameters that Change from the Default Settings with E3-01 [M2 Control Method Selection]

11.18 Parameters that Change from the Default Settings with
E3-01 [M2 Control Method Selection]
The values for the parameters in these tables depend on the values for parameter E3-01. When you change the
setting for E3-01, the default settings will change.
No.
Name
C3-21
M2 Slip Comp Gain
C3-22
M2 Slip Comp DelayTime
E3-04
M2 Max Out Frequency
E3-05
M2 Max Out Voltage
E3-06
M2 Base Frequency
E3-07
M2 Mid A Frequency
E3-08
M2 Mid A Voltage
E3-09
M2 Min Out Frequency
E3-10
M2 Min Out Voltage
E3-11
M2 Mid B Frequency
E3-12
M2 Min Out Voltage
E3-13
M2 Base Voltage
*1
This is the value for 200 V class drives. Double the value for 400 V class drives.
SIEPCYEUOQ2V01A Q2V Technical Manual
Range
Unit
0.0 - 2.50
0.1
0 - 10000
1 ms
40.0 - 590.0
0.1 Hz
0.0 - 255.0
0.1 V
*1
0.0 - 590.0
0.1 Hz
0.0 - 590.0
0.1 Hz
0.0 - 255.0
0.1 V
*1
0.0 - 590.0
0.1 Hz
0.0 - 255.0
0.1 V
*1
0.0 - 590.0
Determined by o1-04
0.0 - 255.0
0.1 V
*1
0.0 - 255.0
0.1 V
*1
Motor 2 Control Method (setting value of E3-01)
V/f
(0)
0.0
2000
60.0
200.0
60.0
3.0
15.0
1.5
9.0
0.0
0.0
0.0
OLV
(2)
1.0
200
60.0
200.0
60.0
3.0
11.0
0.5
2.0
0.0
0.0
0.0
11
407