Control Circuit Terminal Connections

Connections to Inverter control circuit terminals are shown in Fig 2.23.
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-function
Multi-step speed
inputs*
1
setting 1
Multi-step speed
Defaults
setting 2
Jog frequency selection
Pulse train input
Frequency
setter
External
frequency
0 to 10 V
references*
3
4 to 20 mA
RS-485/422
communications
Fig 2.23 Control Circuit Terminal Connections (Asian Models)
CN5 (NPN setting)
Shield terminal
Master speed
pulse train
Frequency setting
0 to 32 kHz (3 kΩ)
adjustment
High level: 3.5 to 13.2 V
input
Frequency setting power
+15 V 20 mA
Master speed reference
0 to 10 V (20 kΩ)
Master speed reference
4 to 20 mA (250 W)
[0 to 10 V (20 kΩ) input]
Terminating
resistance
Wiring Control Circuit Terminals for Asian Models
Pulse train output
0 to 32 kHz (2.2 kΩ)
Default: Output frequency
Ammeter adjustment
Multi-function analog output 2
-10 to 10 V 2 mA
Default: Output current
0 to +10 V
Ammeter adjustment
Multi-function analog output 1
-10 to 10 V 2 mA
Default: Output frequency
0 to +10 V
Fault contact output
250 VAC, 1 A max.
30 VDC, 1 A max.
Multi-function output
250 VAC, 1 A max.
30 VDC, 1 A max.
Default: Running signal
Multi-function output 1
Default: Zero
speed
Multi-function output 2
Default:
Frequency
agree signal
Multi-function transistor
outputs (open-collector)*
2
48 VAC, 50 mA
31
2-