Mitsubishi MELSEC Q Series Programming Manual page 1276

Common instruction 1/2
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Number
Name
CH1 external I/O
SD1883
status monitor
App-268
Meaning
• This register stores a value indicating the external I/
O signal status of CH1.
• Unused signal status is fixed at off.
• When Normal Mode is set for Operation Mode
Setting (high-speed counter function parameter), a
value according to the setting configured for
Function Input Logic Setting (high-speed counter
function parameter) is stored in the function input
status. Therefore, when a voltage is applied to the
function input terminal while Negative logic is set for
Function input logic setting, this register turns off.
• When other than A Phase/B Phase is selected for
Count Source Selection (high-speed counter function
parameter), the phase A input status and phase B
input status are fixed at off.
b15
CH1 external I/O
status monitor
Explanation
to
b7
b6
b5
b4
b3
b2 b1 b0
0
0/1
0/1 0/1 0/1 0/1 0/1 0/1
Phase Z input
status
0: OFF
1: ON
Function input
status
0: OFF
1: ON
Latch counter
input status
0: OFF
1: ON
Phase A input
status
0: OFF
1: ON
Phase B input
status
0: OFF
1: ON
Coincidence
output No.1
0: OFF
1: ON
Coincidence
output No.2
0: OFF
1: ON
Fixed to 0.
Corres-
ponding
Set by
ponding
ACPU
(When Set)
D9
S
(Every END
New
processing)
Corres-
CPU
LCPU