Configuring The Period Of Strobe Light Activation; Enabling Siren Activation Upon Telephone Line Failure - Visonic PowerMaster-10 Installer's Manual

Fully supervised wireless alarm control system
Hide thumbs Also See for PowerMaster-10:
Table of Contents

Advertisement

4.6.3 Configuring the Period of Strobe Light Activation

Here you can define the period of strobe light activation when the siren is in alarm state.
Options: 5 minutes, 10 minutes, 20 minutes (default), 40 minutes and 60 minutes.
To Configure the Period of Strobe Light Activation
1.
03:CONTROL PANEL
2.
01:ENTRY DELAY 1
or
3.
40:STROBE TIME
4.
20 minutes
or
5.
6.
40:STROBE TIME

4.6.4 Enabling Siren Activation upon Telephone Line Failure

Here you determine whether the siren will be activated or not when the telephone line fails during system armed
state. Available options are: enable on fail, disable on fail (default).
To Enable Siren Activation upon Telephone Line Failure
1.
03:CONTROL PANEL
2.
01:ENTRY DELAY 1
or
3.
27:SIREN ON LINE
4.
disable on fail
or
5.
6.
27:SIREN ON LINE
D-303145
Repeat steps 1 to 4 of section 4.2 "Entering the Installer Menu".
Select between "5 minutes", "10 minutes", "20 minutes", "40
minutes" and "60 minutes".
You can now press the
menu in "
03:CONTROL PANEL
"
".
<OK> TO EXIT
Repeat steps 1 to 4 of section 4.2 "Entering the Installer Menu".
Select between "disable on fail" and "enable on fail".
You can now press the
menu in "
03:CONTROL PANEL
"
".
<OK> TO EXIT
or
button to program any other
" or press the
or
button to program any other
" or press the
button to take you to
button to take you to
35