Automatic Remote Setting Of 43R; Automatic Acknowledge Setting - Toshiba GSC1000-C Operation Manual

Substation automation system
Table of Contents

Advertisement

Click 43R button to be changed
SCMS5L

Automatic Remote setting of 43R

8.2.5
When the 43R automatic Remote setting function of the setting file is set to ON, the 43R condition set as
Local is automatically changed to Remote when logs out the System Menu.

Automatic Acknowledge setting

8.2.6
When all 43R conditions are set to Remote, Alarm List becomes ALL Ack with automatically. If at least one
of 43R conditions is set to Local, it will not become ALL Ack with automatically.
2) To change the state of 43R from the Overview
or System window, click the 43R button to be
changed. The 43R selection/control dialog is
displayed. Change the 43R condition follow the
previous chapter.
Note) If the 43R button on the System Menu
is clicked while the selection/control dialog is
displayed, the selection control dialog will not
be displayed furthermore.
3) New 43R condition is displayed.
365