43R" Setting By Each Bay Unit - Toshiba GSC1000-C Operation Manual

Substation automation system
Table of Contents

Advertisement

"43R" setting by each BAY unit

8.2.3
The control right can be set for each BAY unit in the substation. How to set the 43R control right is shown
below. When 43R set to Local, only equipment of BAY that belongs 43R set to Local can be controlled from
the HMI. And, when 43R set to Remote, only equipment of BAY that belongs 43R set to Remote can be
controlled from the RCC.
TOSHIBA
If 43RCC is not set, S43R is displayed left-justified.
6) The column of Status of the S43R dialog is
changed to SCMS.
1) Display the main menu. S43R button displayed
in main menu is gray background. Click S43R
button.
361
6F2M2000