Displaying the BIBO and LED Status of IED
4.60
How to display the BIBO and LED Status of IED is indicated below.
BIBO/LED Status...
3) BIBO/LED Monitoring window is displayed.
This function is applied to BCU/BCPU200 and G2 series
protection relay made by Toshiba. The status of DC-AI
and DC-AO is out of indication scope. When using the
IED other than the above, the selection of BIBO/LED
status from context menu can not be performed.
126
1)
Click System in the main menu bar.
2)
The System window is displayed.
Right-click the IED symbol that to be
displayed the BIBO/LED status. And
then select BIBO/LED Status from
the displayed context menu.
6F2M2000