Toshiba GSC1000-C Operation Manual page 390

Substation automation system
Table of Contents

Advertisement

OWS/
EWS
System
window
Online
Alarm
BCU/BCPU failure message is displayed.
window
Causes
BCU/BCPU error
Remedies
Check the following :
1. BCU/BCPU board failure, or LCD panel failure
2. Database mismatch between BCU/BCPU and server
Match the database of BCU/BCPU and that of the server.
OWS/
EWS
System
window
Alarm
Transmission error between BCU/BCPU and ESW is displayed.
window
Causes
BCU/BCPU transmission unit error, or transmission failure between ESW and BCU
Remedies
Check the following :
1. Check that LAN cable connecting BCU/BCPU and ESW is properly inserted to the
connector.
2. Check for BCU/BCPU board failure.
Station
Common
Station
Common
This portion is displayed in red.