Alarm and Event window
Phenomenon
Display date is indicated
in reversed order.
No storage is possible
even if the Save button is
clicked.
No loading is possible
even if the Load button is
clicked.
No printing is possible
even if the Print button is
clicked.
No display on the
window.
(Alarm, or Event window)
Cause
Sorting is carried out in reversed
order by clicking "Date Time" title.
HMI (PC) application error.
SC application error
Insufficient space in HDD of HMI.
(PC)
HMI (PC) application error
SC application error.
Saved file is damaged.
HMI (PC) application error
SC application error.
HMI (PC) application error
SC application error.
382
Corrective action
Click "Date Time" again to carry out
sorting.
Or, click the LATEST button in the
corresponding screen to return to
the initial status.
Restart HMI (PC).
Restart SC.
Delete unnecessary files in HMI
(PC) or add another HDD.
Restart HMI (PC).
Restart SC.
Check the file contents. If the file is
damaged, correct the file and load it
again.
Restart HMI (PC).
Restart SC.
Restart HMI (PC).
Restart SC.