Toshiba GSC1000-C Operation Manual page 394

Substation automation system
Table of Contents

Advertisement

OWS/
EWS
System
window
GPS
Alarm
GPS clock failure message is displayed.
window
Causes
Transmission error between GPS clock and ESW
Remedies
Check the following :
1.Check whether GPS clock power is OFF.
2.Check that communication cable connecting GPS clock and ESW is properly connected
to the connecting port.
OWS/
EWS
System
window
Online
GPS
GPS
Alarm
GPS clock failure message is displayed.
window
Causes
GPS clock detects any error.
Remedies
Check the following :
1.Check whether "ALARM" LED on the front panel of GPS clock is lit or not.
If it is lit, the GPS clock detects an error.
Refer to "Technical Information Operating Instructions M300/GPS" of GPS clock for the
details of the error.
This portion is displayed in red
This portion is displayed in red.