6) Event list:
Red:
Major failure (Event level 01 and 02)
Orange: Minor failure (Event level 03 and 04)
Black: General event and operation recorded event (Event level 05 and 06)
Green: Recovered event
a)
c)
d)
e)
b)
a) Failure symbol:
b) Lv. :
Displays event level.
c) T:
Indicates the test discrimination.
d) Q:
Indicates the quality of date.
e) Date Time:
f) Voltage:
g) Bay:
h) Object Text:
i) Status:
Area to display the event data.
f)
g)
: Heavy (event level 01 and 02)
: Light (event 03 and 04)
01: Major failures such as protection relay operation
02: Major failures in SAS
03: Minor failures such as switchgear or transformer
04: Minor failures in SAS
05: General event
06: Operation recorded event
Blank: Event message in Online mode
T
: Event message in Test mode
Blank: Date and time given by the IED synchronized with master clock.
(GPS 1, 2, SC-A or SC-B)
*
: Date and time not synchronized with master clock
Displays date and time.
Displays the voltage level
Displays the bay name.
Displays the event messages.
Displays the device status.
h)