Phenomenon
"X" is automatically
displayed before clicking
Print button.
Screen switch is
abnormally slow.
(3)
Problems in the OVERVIEW window
Phenomenon
Whole system is not
displayed.
Equipment symbol is
white with "?"
Color frame is displayed
in the Bay label.
No reaction takes place
even if the mouse is
moved to the Bay label.
Going over to the Bay
single line window is
impossible.
Measurement value is
displayed in abnormal
color.
Measurement value is
displayed "?".
Cause
SC application error.
HMI (PC) application error
SC application error.
HMI (PC) application error.
Cause
HMI (PC) application error.
Incorrect bay allocation at
Equipment DB maintenance.
HMI (PC) application error.
Incorrect data sent from IED.
Incorrect device symbol
allocation at Equipment DB
maintenance.
Color frame may be drawn as a
figure by Drawing Tool.
Incorrect device symbol
allocation at Equipment DB
maintenance.
HMI (PC) application error
Incorrect device symbol
allocation at Equipment DB
maintenance.
HMI (PC) application error.
Incorrect data sent from IED.
Incorrect device symbol
allocation at Equipment DB
maintenance.
HMI (PC) application error.
SC application error.
HMI (PC) application error.
SC application error.
Incorrect data sent from IED.
Incorrect measurement symbol
allocation at Equipment DB
maintenance.
HMI (PC) application error.
SC application error.
376
Corrective action
Restart SC.
Restart HMI (PC).
Restart SC.
Restart HMI (PC).
Corrective action
Restart HMI (PC).
Check the maintenance contents in
equipment DB.
Restart HMI (PC).
Check the IED status and data.
Check the maintenance contents
executed on Equipment DB.
Check the maintenance contents
executed on Equipment DB.
Check the maintenance contents
executed on Equipment DB.
Restart HMI (PC).
Check the maintenance contents
executed on Equipment DB.
Restart HMI (PC).
Check the IED status and data.
Check the maintenance contents
executed on Equipment DB.
Restart HMI (PC).
Restart SC.
Restart HMI (PC).
Restart SC.
Check the IED status and data.
Check the maintenance contents
executed on Equipment DB.
Restart HMI (PC).
Restart SC.
6F2M2000