Set the Configuration Jumpers

Before installing the 1756-MVI module in the chassis, set the
module's configuration jumpers on the module's printed circuit
board.
1. The module ships with the Setup jumper in the Setup position
(see the figure on the following page). The Setup jumper
causes the module to boot with console port PRT1 enabled at
19200 baud, no parity, 8 data bits and 1 stop bit.
Note: When the Setup jumper is removed, the module will
boot with the configuration set in the BIOS Setup Menu. This
configuration is described in detail in the Quick Start section
of this manual. See "Configure the Manual" on page 16.
2. To enable communications on Port 2 and Port 3, place a
jumper in the RS232, RS422, or RS485 position for each port.
The module ships with the jumpers in the RS232 position
(default).