Overview; Install The Module; Set The Network Address - Rockwell Automation Allen-Bradley ArmorBlock 1732E-IB8M8SOER User Manual

Ethernet/ip dual port 8-point sequence of events input and scheduled output modules
Table of Contents

Advertisement

Overview

Install the Module

Install Your Module
This chapter shows you how to install and wire the ArmorBlock EtherNet/IP
Dual Port 8-point Sequence of Events Input and Scheduled Output Modules.
The only tools you require are a flat or Phillips head screwdriver and drill. This
chapter includes the following topics:
Topic
Install the Module

Set the Network Address

Mount the Module
Wire the Module
Power Connectors
To install the module:
Set the network address.
Mount the module.
Connect the I/O, Network, and Auxiliary cables to the module.
Set the Network Address
The I/O block ships with the rotary switches set to 999 and DHCP enabled. To
change the network address, you can do one of the following:
Adjust the node address switches on the front of the module.
Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
Retrieve the IP address from nonvolatile memory.
The I/O block reads the switches first to determine if the switches are set to a
valid number. To set the network address:
1. Remove power.
2. Remove the switch dust caps.
3. Rotate the three (3) switches on the front of the module using a small
blade screwdriver.
4. Line up the small notch on the switch with the number setting you wish
to use.
Valid settings range from 001...254.
5. Replace switch dust caps. Make sure not to over tighten.
6. Reapply power.
Rockwell Automation Publication 1732E-UM003D-EN-E - November 2021
Chapter
Page
21
21
22
23
24
4
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Allen-bradley armorblock 1732e-ob8m8sr

Table of Contents