  • Page 1 Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...
  • Page 2 Allen-Bradley User Manual FLEX Integra Analog Modules (Cat. No. 1793-IE4, -IE4S, -OE2, -OE2S, -IE2XOE1 and -IE2XOE1S) Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 3 Important: Identifies information that is critical for successful application and understanding of the product. DeviceNetManager, Allen-Bradley, FLEX I/O and FLEX Integra are trademarks of Rockwell Automation ControlNet is a trademark of ControlNet International. DeviceNet is a trademark of Open DeviceNet Vendor Association, Inc.
  • Page 4 Preface Using This Manual Purpose of this Manual This manual shows you how to use your FLEX Integra Analog modules with Allen-Bradley programmable controllers. The manual helps you install, program and troubleshoot your modules. Audience You must be able to program and operate an Allen-Bradley programmable controller to make efficient use of your FLEX Integra modules.
  • Page 5 Using This Manual Conventions We use these conventions in this manual: In this manual, we show: Like this: that there is more information about a topic in another chapter in this manual that there is more information about the topic in another manual For Additional Information For additional information on FLEX Integra and FLEX I/O systems and...
  • Page 6 Using This Manual Publications Catalog Voltage Description Installation User Number Instructions Manual 1794-IB10XOB6 24V dc 10 Input/6 Output Module 1794-5.24 1794-IE8 24V dc Selectable Analog 8 Input Module 1794-5.6 1794-6.5.2 1794-OE4 24V dc Selectable Analog 4 Output Module 1794-5.5 1794-IE4XOE2 24V dc 4 Input/2 Output Analog Module 1794-5.15...
  • Page 7: Table Of Contents

    Table of Contents Preface Using This Manual Purpose of this Manual ....... . . P-1 Audience .
  • Page 8 Chapter 4 Writing Configuration to and Chapter Objectives ........4-1 Configuring Your Analog Module .
  • Page 9 Chapter 6 Input, Status, Output and What this Chapter Contains ......6-1 About the ControlNet Adapter .
  • Page 10: Chapter Objectives

    Chapter Overview of FLEX Integra and your Analog Modules Chapter Objectives In this chapter, we tell you about: • what the FLEX Integra system is and what it contains • types of FLEX Integra analog modules • how FLEX Integra analog modules communicate with programmable controllers •...
  • Page 11 Overview of FLEX Integra and your Analog Modules Types of FLEX Integra Modules We describe the following FLEX Integra Analog modules in this user manual: Catalog Number Voltage Inputs Outputs Description analog – 4 input, single-ended, non-isolated; 1793-IE4 24V dc –...
  • Page 12 Overview of FLEX Integra and your Analog Modules Figure 1.1 An Example of Communication Between an Adapter and an Analog Input Module The adapter transfers your configuration data External devices transmit to the module using a BTW. analog signals to the module. Flexbus Allen-Bradley Allen-Bradley...
  • Page 13 Overview of FLEX Integra and your Analog Modules Features of your Analog Each module has a unique label identifying its wiring and module type. A removable label provides space for writing individual designations per Modules your application. 1793-IE4S 1793-IE2XOE1 1793-OE2 4 INPUT ANALOG 2 CH ANALOG OUTPUT 2 INPUT/1 OUTPUT ANALOG...
  • Page 14: Before You Install Your

    Chapter How to Install Your Analog Module Chapter Objectives In this chapter, we tell you about: • how to install your module • how to wire your module • the indicators Before You Install Your Before installing your analog module in the I/O chassis: Analog Module You need to: As described under:...
  • Page 15: Low Voltage Directive

    How to Install Your Analog Module Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: •...
  • Page 16 How to Install Your Analog Module 2. Position the module on the 35 x 7.5mm DIN rail A (A-B pt. no. 199-DR1). Rotate the module onto the DIN rail with the top of the rail hooked under the lip on the rear of the module. 30720-M 3.
  • Page 17 How to Install Your Analog Module 6. To remove an Integra module, you must work from the right side and remove one module at a time. To disengage a module from its neighbor, place a common flat-bladed screwdriver between the 2 modules and turn 1/4 turn to separate the modules.
  • Page 18: Connecting Wiring For The Analog Modules

    How to Install Your Analog Module Connecting Wiring for the Connecting Wiring for the 1793-IE4 Input Module Analog Modules This module is available with 2 styles of connectors; screw-cage and spring clamp. Refer to the wiring figure below. 1793-IE4 1793-IE4S Ch 0 Ch 1 Ch 0 Ch 1...
  • Page 19: Connecting Wiring For The 1793-Oe2 Output Module

    How to Install Your Analog Module Table 2.A Wiring connections for the 1793-IE4 Analog Module Label Channel Signal Type Signal Return Markings Current Voltage Current Voltage Current Voltage Current Voltage 24V dc Common Terminals 0, 1, 6, 9, and 14 are connected together in the module.
  • Page 20 How to Install Your Analog Module $77(17,21 &RQQHFW RQO\  YROWDJH RU FXUUHQW VLJQDO SHU FKDQQHO 'R QRW FRQQHFW ERWK YROWDJH DQG FXUUHQW RQ RQH FKDQQHO 2. Connect +24V dc to terminal 8 on row B 3. Connect 24V common to terminal 0 on row A. 4.
  • Page 21 How to Install Your Analog Module Table 2.B Wiring connections for the 1793-OE2 Analog Module Channel Type Label Marking Signal Return Current Signal Current Common Voltage Signal Voltage Common Current Signal Current Common Voltage Signal Voltage Common 24V dc Common Terminals 0, 1, 6, 7, 9 and 14 +24V dc Terminals 8 and 15 are internally connected to +V.
  • Page 22 How to Install Your Analog Module 5. Connect +24V dc to terminal 8 on row B 6. Connect 24V dc common to terminal 0 on row A. 7. If daisy-chaining +24V dc from this module to the next FLEX Integra module, connect a jumper from terminal 15 to terminal 8 on the next FLEX Integra module.
  • Page 23: Module Indicators

    2-10 How to Install Your Analog Module Module Indicators The analog modules have status indicators that are on when power is applied to the module An insertable label is supplied to identify your inputs and outputs. 1793-IE2XOE1 1793-IE4S 1793-OE2 2 INPUT/1 OUTPUT ANALOG 2 CH ANALOG OUTPUT 4 INPUT ANALOG INPUT...
  • Page 24: Chapter 3 Chapter Objectives

    Chapter Module Programming Chapter Objectives In this chapter, we tell you about: • analog data format • block transfer programming • sample programs for the PLC-3 and PLC-5 processors Block Transfer Your module communicates with the processor through bidirectional block transfers.
  • Page 25: Sample Programs For Flex Integra Analog Modules

    Module Programming Sample programs for FLEX The following sample programs show you how to use your analog module efficiently when operating with a programmable controller. Integra Analog Modules These programs show you how to: • configure the module • read data from the module •...
  • Page 26 Module Programming Figure 3.2 PLC-3 Family Sample Program Structure for a 1793-OE2 Module Enable BLOCK XFER READ Program Action Block Transfer RACK: Read Done Bit GROUP: Done B6:0 At power-up in RUN mode, or when the MODULE: processor is switched from PROG to RUN, CONTROL: #B6:0 the user program enables a block transfer...
  • Page 27: Plc-5 Programming

    Module Programming PLC-5 Programming The PLC-5 program is very similar to the PLC-3 program with the following exceptions: • block transfer enable bits are used instead of done bits as the conditions on each rung. • separate block transfer control files are used for the block transfer instructions.
  • Page 28: Plc-2 Programming

    Module Programming Figure 3.6 PLC-5 Family Sample Program Structure for the 1793-IE2XOE1 BTW Enable Bit BTR Enable Bit Program Action N16:5 N16:0 BLOCK TRANSFER READ RACK: GROUP: At power-up in RUN mode, or when the processor is switched from PROG to RUN, MODULE: CONTROL: N16:0...
  • Page 29: Chapter Summary

    Module Programming Refer to Appendix B for a table of values for various current and voltage modes. Appendix B also includes an example of scaling. Chapter Summary In this chapter, you learned how to program your programmable controller. You were given sample programs for your PLC-3 and PLC-5 family processors.
  • Page 30: Configuring Your Analog Module

    Chapter Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Chapter Objectives In this chapter, we tell you about: • configuring your module’s features • entering your data • reading data from your module • read block format Configuring Your Analog Note: You must use a 1794-ASB series D or later remote I/O adapter to communicate with the 1793 FLEX Integra analog modules.
  • Page 31: Range Selection

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Range Selection Individual input channels are configurable to operate with the following voltage or current ranges: Bit Settings Ranges Configure Full Range Select 0-10V dc/0-20mA 4-20mA –10 to +10V dc When configured to Off, individual output channels will drive 0V/0mA.
  • Page 32: Analog Input Module (1793-Ie4 And -Ie4S) Read

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 8 Input Analog Module (Cat. No. 1793-IE4 and -IE4S) Module Image Input Data Channel 0 Input Data Channel 1 I/O Image Input Data Channel 2 Input Size Input Data Channel 3 1 to 9 Words Reserved...
  • Page 33: Module Read

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Word/Bit Descriptions for the 1793-IE4 and -IE4S Analog Input Module Read Decimal Bit Word Definition (Octal Bit) Bits 00-14 Channel 0 analog data – 12-bit left justified two’s complement number; (00-16) unused lower bits are zero;...
  • Page 34: Range Selection Bits For The 1793-Ie4 And -Ie4S Analog Input Module

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Range Selection Bits for the 1793-IE4 and -IE4S Analog Input Module Channel No. Channel 0 Channel 1 Channel 2 Channel 3 Decimal Bits (Octal Bits) (10) (11) (12) (13)
  • Page 35: Analog Output Module (1793-Oe2 And -Oe2S) Read

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Analog Output Module (1793-OE2 and -OE2S) Read Word/Dec. Bit Word/Octal Bit Read Word 0 Not used – set to 0 Where: W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.) PU = Power up bit Bit/Word Descriptions for the 1793-OE2 and -OE2S Analog Output Module Read Decimal Bit...
  • Page 36: Range Selection Bits For The 1793-Oe2 And -Oe2S Analog Output Module (Word 5)

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Range Selection Bits for the 1793-OE2 and -OE2S Analog Output Module (Word 5) Channel No. Channel 0 Channel 1 Decimal Bits (Octal Bits) 08 (10) 09 (11) 4-20mA 0-10V dc/0-20mA –10 to +10V dc...
  • Page 37: Analog Combo Module (1793-Ie4Xoe1) Read

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Decimal Bit Word Definition (Octal Bit) Words 12-13 Bits 00-15 Reserved (00-17) 2 Input/1 Output Analog Combo Module (Cat. No. 1793-IE2XOE1 and -IE2XOE1S) Module Image I/O Image Input Data Channel 0 Input Size Input Data Channel 1...
  • Page 38: Configuration Block

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Decimal Bit Word Definition (Octal Bit) Word 4 Underrange bits (U) for individual channels (4-20mA current input only)- Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1. Bits 00-01 When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
  • Page 39: Range Selection Bits For The 1793-Ie2Xoe1 And -Ie2Xoe1S Analog Combo Module

    4-10 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter Range Selection Bits for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module Input Input Output Channel No. Channel 0 Channel 1 Channel 0 Decimal Bits (Octal Bits) (10) (11) (14)
  • Page 40: Chapter Summary

    Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 4-11 Decimal Bit Word Definition (Octal Bit) Words 4 Not used – set to 0. and 5 Bits 00-14 Channel 0 Safe State analog value – 12-bit left justified two’s complement number; (00-16) unused lower bits are zero;...
  • Page 41: Chapter 5 Chapter Objectives

    Chapter How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter Chapter Objectives In this chapter, we tell you about: • DeviceNetManager software • I/O structure • image table mapping • factory defaults About DeviceNetManager DeviceNetManager software is a tool used to configure your FLEX I/O DeviceNet adapter and its related modules, including any FLEX Integra Software modules.
  • Page 42 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter Adapter Input Status Word The input status word consists of: • I/O module fault bits – 1 status bit for each slot • node address changed – 1 bit •...
  • Page 43: System Throughput

    How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter System Throughput System throughput, from analog input to backplane, is a function of: • the data format selected • the type and mode of sensors selected • whether filtering is selected The A/D converter which converts channel 0 through 7 analog data to a digital word provides a programmable single low pass filter.
  • Page 44 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter Analog Input Module (1793-IE4 and -IE4S) Read Word/Dec. Bit Word/Octal Bit Read Word 1 Analog Value Channel 0 Word 2 Analog Value Channel 1 Word 3 Analog Value Channel 2 Word 4 Analog Value Channel 3 Word 5...
  • Page 45 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter Range Selection Bits for the 1793-IE4 and -IE4S Analog Input Module Channel No. Channel 0 Channel 1 Channel 2 Channel 3 Decimal Bits (Octal Bits) (10) (11) (12) (13) 0-10V dc/0-20mA...
  • Page 46 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter 2 Output Analog Module (Cat. No. 1793-OE2 and -OE2S) I/O Image Module Image Input Size 0 or 1 Word Read Diagnostics Not used Analog Data Channel 0 Analog Data Channel 1 Reserved Reserved...
  • Page 47 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter Analog Output Module (1793-OE2 and -OE2S) Write Configuration Block Word/Dec. Bit Word/Octal Bit Write Word 1 Analog Data – Channel 0 Word 2 Analog Data – Channel 1 Word 3 Reserved Word 4...
  • Page 48 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter Word/Bit Descriptions for the 1793-OE2 and -OE2S Analog Output Module Write Decimal Bit Word Definition (Octal Bit) Bits 00-14 Channel 0 analog data – 12-bit left justified two’s complement number; unused (00-16) lower bits are zero;...
  • Page 49 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter 2 Input/1 Output Analog Combo Module (Cat. No. 1793-IE2XOE1 and -IE2XOE1S) odu e I/O Image Input Data Channel 0 Input Size Input Data Channel 1 0 to 5 Words Read Reserved Reserved...
  • Page 50 5-10 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter Decimal Bit Word Definition (Octal Bit) Word 5 Underrange bits (U) for individual channels (4-20mA current input only)- Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1. Bits 00-01 When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
  • Page 51: Defaults

    How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter 5-11 Word/Bit Descriptions for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module Write Decimal Bit Word Definition (Octal Bit) Bits 00-14 Channel 0 analog data – 12-bit left justified two’s complement number; unused (00-16) lower bits are zero;...
  • Page 52: Chapter Summary

    5-12 How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter You can change the I/O data size for a module by reducing the number of words mapped into the adapter module, as shown in “real time sizes.” Real time sizes are the settings that provide optimal real time data to the adapter module.
  • Page 53: What This Chapter Contains

    Chapter Input, Status, Output and Configuration Files using ControlNet What this Chapter Contains Read this chapter to familiarize yourself with input, output and configuration files for analog I/O modules on ControlNet.This chapter talks about: • the ControlNet Adapter • I/O structure •...
  • Page 54: Scheduled Data-Transfer

    Input, Status, Output and Configuration Files using ControlNet Scheduled Data-Transfer Scheduled data transfer: • is continuous. • is asynchronous to the controller program scan. • occurs at the actual rate displayed in the Actual Packet Interval field on the programming software ControlNet I/O mapping (monitor) screen Unscheduled Data-Transfer Unscheduled operations include: •...
  • Page 55: I/O Structure

    Input, Status, Output and Configuration Files using ControlNet I/O Structure Output data is received by the adapter in the order of the installed I/O modules. The output data for slot 0 is received first, followed by the output data for slot 1, and so on up to slot 7. The first word of input data sent by the adapter is the Adapter status word.
  • Page 56: Safe State Data

    Input, Status, Output and Configuration Files using ControlNet As an example, in a PLC-5 system, the adapter input status word bit descriptions are shown in the following table. Bit Description: Bit: Explanation: This bit is set (1) when an error is detected in slot position 0. This bit is set (1) when an error is detected in slot position 1.
  • Page 57: Communication Fault Behavior

    Input, Status, Output and Configuration Files using ControlNet Communication Fault Behavior You can configure the adapter response to a communication fault for each I/ O module in its system. Upon detection of a communication fault, the adapter can: • leave the module output data in its last state (hold last state) •...
  • Page 58: Input Module

    Input, Status, Output and Configuration Files using ControlNet 4 Input Analog Module (Cat. No. 1793-IE4 and -IE4S) Module Image Input Data Channel 0 Input Data Channel 1 ControlNet Files Input Data Channel 2 Input File Size Input Data Channel 3 1 to 9 Words Reserved Reserved...
  • Page 59: Range Selection Bits For The 1793-Ie4 And -Ie4S Analog Input Module

    Input, Status, Output and Configuration Files using ControlNet Range Selection Bits for the 1793-IE4 and -IE4S Analog Input Module Channel No. Channel 0 Channel 1 Channel 2 Channel 3 Decimal Bits (Octal Bits) (10) (11) (12) (13) 0-10V dc/0-20mA 4-20mA –10 to +10V dc C = Configure select bit F = Full range bit...
  • Page 60: Output Module Read

    Input, Status, Output and Configuration Files using ControlNet ABit/Word Descriptions for the 1793-OE2 and -OE2S Analog Output Module Read Input Decimal Bit Definition Words (Octal Bit) Current outputs only – When set (1), the wire on the output is broken or the Bits 00-01 load resistance is too high.
  • Page 61: Configuration Word/Bit Descriptions For The 1793-Oe2 And -Oe2S Analog Output Module Write

    Input, Status, Output and Configuration Files using ControlNet Configuration Word/Bit Descriptions for the 1793-OE2 and -OE2S Analog Output Module Write Configuration Decimal Bit Definition Word (Octal Bit) Multiplex control bits (M) for individual channels. These bits control the safe state analog outputs. – Bit 00 corresponds to output channel 0, bit 01 corresponds to output channel 1, and so on.
  • Page 62: Range Selection Bits For The 1793-Ie2Xoe1And -Ie2Xoe1S Analog Combo Module

    6-10 Input, Status, Output and Configuration Files using ControlNet Input Decimal Bit Definition Word (Octal Bit) Words 2 Reserved and 3 Word 4 Underrange bits (U) for individual channels (4-20mA current input only)- Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1. Bits 00-01 When set (1), indicates either a broken or open input wire, or input current at or below 4mA.
  • Page 63: Chapter Summary

    Input, Status, Output and Configuration Files using ControlNet 6-11 Configuration Word/Bit Descriptions for the 1793-IE2XOE1 and -IE2XOE1S Analog Combo Module Configuration Decimal Bit Definition Word (Octal Bit) Multiplex control bits (M) for individual channel. This bit controls the safe state analog outputs–...
  • Page 64: Appendix A Specifications

    Appendix Specifications Specifications - 4 Input Analog Module, Cat. No. 1793-IE4 and -IE4S Module Type 4 analog inputs 1793-IE4 - 16 screw-cage terminals 1793-IE4S - 16 spring-clamp terminals Module Location DIN rail mounting Number of Channels Data Format 16-bit 2’s complement, left-justified Conversion Type Successive approximation Conversion Rate...
  • Page 65 Specifications Specifications - 4 Input Analog Module, Cat. No. 1793-IE4 and -IE4S Thermal Dissipation 3.4 BTU/hr @ 31.2V dc Indicators 1 green power indicators External dc Power Voltage 19.2-31.2V dc (5% ac ripple) Current 60mA maximum Dimensions 2.72H x 3.15D x 2.17W (mm) (69H x 80D x 55W) Environmental Conditions...
  • Page 66 Specifications Specifications - 2 Output Analog Module, Cat. No. 1793-OE2 and -OE2S Module Type 2 analog output 1793-OE2 - 16 screw-cage terminals 1793-OE2S - 16 spring-clamp terminals Module Location DIN rail mounting Number of Channels 2 out - nonisolated Output Resolution 12-bits plus sign Voltage...
  • Page 67 Specifications Specifications - 2 Input/1 Output Analog Module, Cat. No. 1793-IE2XOE1 and -IE2XOE1S Module Type 2 analog inputs, 1 analog output 1793-IE2XOE1 - 16 screw-cage terminals 1793-IE2XOE1S - 16 spring-clamp terminals Module Location DIN rail mounting Number of Channels 3 - 2 in, 1 out - nonisolated Input Resolution 12-bits - unipolar;...
  • Page 68 Specifications Specifications - 2 Input/1 Output Analog Module, Cat. No. 1793-IE2XOE1 and -IE2XOE1S Accuracy Drift Voltage Terminal 0.0045% FS per Current Terminal 0.0069% FS per Isolation Voltage Channel to system - 850V dc for 1s Channel to channel - None General Flexbus Current 20mA maximum...
  • Page 69: Appendix B Two's Complement Binary

    Appendix Data Table Formats Two’s Complement Binary Two’s complement binary is used when performing mathematical calculations internal to the processor. To complement a number means to change it to a negative number. For example, the following binary number is equal to decimal 22. 10110 = 22 First, the two’s complement method places an extra bit (sign bit) in the...
  • Page 70: Analog Data Format

    Data Table Formats Analog Data Format The data returned from the analog-to-digital converter in the module is 12-bit resolute. This value is left-justified into a 16-bit field, reserving the most significant bit for a sign bit. 11 10 09 08 07 06 05 04 03 02 01 00 A/D Unipolar Data Analog Value 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00...
  • Page 71 Data Table Formats Scaling Example To scale your data to a different range: • SLC 500 - use the scaling instruction. • PLC-5 - determine a constant (slope) by dividing the desired range by the actual range. Multiply the result by your data, and add or subtract any offset.
  • Page 72 Index FRQILJXUDWLRQ EORFN DGDSWHU LQSXW VWDWXV ZRUG 5-1 block transfer write DQDORJ PRGXOHV 1793-IE4 5-4 types 1-2 1793-IE4 4-4 1793-OE2 5-7 1793-OE2 4-6 ELWZRUG GHVFULSWLRQ FRQILJXUDWLRQ ZRUG ELWZRUG GHVFULSWLRQ 4 output/4 input module 4-6 5-6 1793-IE2XOE1 6-11 block transfer read 1793-OE2 6-9 FRQILJXUDWLRQ ZRUGELW GHVFULSWLRQ 1793-IE2XOE1 4-8...
  • Page 73 PLC-3 3-2 IHDWXUHV PLC-5 3-4 configuring 4-1 of the module 1-4 UDQJH selecting 4-2 ,2 PRGXOH IDXOW 5-2 6-4 UDQJH VHOHFWLRQ LQGLFDWRUV 1793-IE2XOE1 4-10 5-10 6-10 status 2-10 1793-IE4 5-5 6-7 LQSXW UDQJHV 4-2 1793-IE4 4-5 program selectable 1-2 1793-OE2 5-7 6-8 LQSXW VWDWXV ZRUG 5-2 6-3 1793-OE2 4-7 LQSXW ZRUG ELWZRUG GHVFULSWLRQ...
  • Page 74 Allen-Bradley Publication Problem Report If you find a problem with our documentation, please complete and return this form. Pub. Name FLEX Integra Analog Modules User Manual Cat. No. 1793-IE4, OE2, IE2XOE1 Pub. No. 1793-6.5.1 Pub. Date April 1999 Part No. 955132-30 Check Problem(s) Type: Describe Problem(s) Internal Use Only...
  • Page 75 PLEASE FASTEN HERE (DO NOT STAPLE) Other Comments PLEASE FOLD HERE NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES BUSINESS REPLY MAIL FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH POSTAGE WILL BE PAID BY THE ADDRESSEE 1 ALLEN BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705 Artisan Technology Group - Quality Instrumentation ...
  • Page 76 Publication 1793-6.5.1 - April 1999 PN 955132-30 © (1999) Rockwell International Corporation. Printed in the U.S.A. Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 77 Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...

Table of Contents