8
Commissioning and preparing to measure
8.1
Network configuration
To restore factory defaults:
Click the Restore Factory Defaults button.
A dialog box requests confirmation to restore the modules to factory default
settings.
Click the OK button.
Cycle power for the entire module chain by turning the power off and then back
on.
The Network LED on each module will flash five times per second while waiting
for DHCP to assign an IP address. The Network LED on each module will flash
twice per second when an address has been assigned.
If a router with a DHCP server is not used the modules need to be manually
programmed to unique static addresses.
Further Information:
Wait for the Network LED to flash twice per second on all modules.
Click the OK button in the dialog box.
MSEsetup performs a broadcast. Each modules Network LED will flash twice per
second until MSEsetup obtains a connection to the module. A dialog box confirms
the number of modules found.
Click the OK button in the dialog box to overwrite the configurable module
settings with a backup file or the Cancel button to skip overwriting the the
settings.
A message is displayed in the Connect screen message area when broadcasting is
finished.
8.1.6

Firewall configuration

MSEsetup uses the UDP protocol for communication with MSE 1000 modules.
By default firewalls may block UDP messages. Network firewall settings may
need to be configured to allow UDP on the ports used by MSEsetup and MSE
1000 modules. Refer to the documentation provided with the firewall software for
additional information.
MSE port assignments:
MSE component
MSEsetup
MSE 1000 mod-
ules
MSEsetup asyn-
chronous thread
86
"Configuring the module chain manually", page 89.
Port
27016
The port can be changed in the Con-
nect screen.
Further Information:
page 79.
27015
This port cannot be changed.
27300
The port can be changed in the Con-
nect screen.
Further Information:
page 79.
"Workstation IP",
"Workstation IP",
HEIDENHAIN | MSE 1000 | Operating Instructions | 10/2015