Communication Errors - HEIDENHAIN MSE 1000 Operating Instructions Manual

Table of Contents

Advertisement

12
Troubleshooting
12.5

Communication errors

12.5
Communication errors
The error
between MSEsetup and MSE 1000 modules. The actual error as well as the module that had the error
and the channel, if applicable, will be shown in the Log screen.
If the troubleshooting procedures described in this section are unsuccessful, see "Network trou-
bleshooting", page 161 for additional information.
Error
Response timeout
Broadcast failed to get a re-
sponse
The binding of the UDP socket
failed
156
Lost communication to the MSE 1000
is sent to the Error screen for communication errors
Cause
A command was sent to a
module and failed to obtain a
response within the timeout
period. The default timeout pe-
riod is 200 ms.
A broadcast returned with no
modules found.
A broadcast could not be start-
ed because the socket failed
to bind. This is usually because
another application is using the
socket and port.
HEIDENHAIN | MSE 1000 | Operating Instructions | 10/2015
Corrective action
Check the power and
network connection to the
modules.
Power cycle the module
chain, see "Power cycling",
page 48.
Perform a reconnect.
Close MSEsetup.
Restart MSEsetup.
Verify that the workstation
IP is on the correct domain.
Verify that communication
to a module is working with
a ping request from the
operating system.
Perform a broadcast when
communication is verified.
Close MSEsetup.
Restart MSEsetup.
Verify that the workstation
IP is on the correct domain.
Verify that communication
to a module is working with
a ping request from the
operating system.
Change the port from
the networking screen if
another application is using
the port.
Perform a broadcast when
communication is verified.