L10 DN INIT. ERR. 1 36 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FFH.
- The value of the local node No. (MAC ID) is out of range.
- The value of the mode switch is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Set the local node number between 0 and 63.
- Set the mode switch to other than D - F.
L10 DN INIT. ERR. 1 39 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FFH.
- Two or more modes that have the same node No. (MAC ID) exist in the network.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Set non-duplicate node Nos.
L10 DN INIT. ERR. 1 E0 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FFH.
- Network power is not being supplied.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Supply the network power (24VDC).
L10 DN INIT. ERR. 1 E1 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FFH.
- Other modules are not found in the network.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Connect other modules in the network.
L10 DN INIT. ERR. 1 F0 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FFH.
- Node No. setting switch or mode switch setting was changed during operation.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Return the node No. setting switch or mode switch
setting to be the original setting.
L11 DN INIT. ERR. 2 02 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The number of input points and output points of the slave node set by parameters are both "0".
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit removed.
Remedy
- Set the number of input points and output points according to the slave node specifications.