【#2051】 check Check
Set the tolerable range of travel distance (deviation distance) while the power is turned OFF.
If the difference of the positions when the power is turned OFF and when turned ON again is larger
than this value, an alarm will be output.
Set "0" to omit the check.
---Setting range---
0 to 99999.999 (mm)
【#2052】 absg28 Width compared by G28
Set the allowable range of the comparison result when comparing the positions during G28 or G30.
0: Not compare
1 to 65535 (in increments of 0.5μm):
---Setting range---
0 to 65535 (0.5μm)
【#2053】 absm02 Width compared by M02
Set the allowable range of the comparison result when comparing the positions during M02 or M30.
0: Not compare
1 to 65535 (in increments of 0.5μm):
---Setting range---
0 to 65535 (0.5μm)
【#2054】 clpush Current limit (%)
Set the current limit value during the stopper operation in the dogless-type absolute position
detection.
The setting value is the ratio of the current limit value to the rated current value.
---Setting range---
0 to 100 (%)
【#2055】 pushf Push speed
Set the feedrate for the automatic initial setting during stopper method.
---Setting range---
1 to 999 (mm/min)
【#2056】 aproch Approach
Set the approach distance of the stopper when deciding the absolute position basic point with the
stopper method.
After using stopper once, the tool returns with this distance, and then use stopper again.
---Setting range---
0 to 999.999 (mm)
【#2057】 nrefp Near zero point +
Set the positive direction width where the near reference position signal is output.
When set to "0", the width will be equivalent to the grid width setting.
---Setting range---
0 to 32.767 (mm)
【#2058】 nrefn Near zero point -
Set the negative direction width where the near reference position signal is output.
When set to "0", the width will be equivalent to the grid width setting.
---Setting range---
0 to 32.767 (mm)
If the difference between the position read by the detector and that in the control unit exceeds
this range, an alarm will be output to stop the machine. The standard setting is 100.
If the difference between the position read by the detector and that in the control unit exceeds
this range, an alarm will be output to stop the machine. The standard setting is 100.
Appendix 1.4 Axis Specifications Parameters