Mitsubishi Electric C70 Setup Manual page 512

Hide thumbs Also See for C70:
Table of Contents

Advertisement

A01 MULTI CPU ERROR 1601
Details
- Voltage of the battery on memory card 1 has dropped below stipulated level.
Remedy
- Change the battery.
A01 MULTI CPU ERROR 1610
Details
- The number of writing to the FLashROM (the standard RAM or the area reserved by the system)
exceeded one hundred thousand times.
(Number of writing>100,000 times)- Voltage of the battery on memory card 1 has dropped below
stipulated level.
Remedy
- Replace the CPU modules.
A01 MULTI CPU ERROR 2000
Details
I/O module information power ON is changed.
- I/O module (or intelligent function module) not installed properly or installed on the base unit.
Remedy
Read the common information of the error using a programming tool, and check and/or change the
module that corresponds to the numerical value (module number) there.
- Alternatively, monitor the special registers SD1400 to SD1431 using GX Developer, and change the
fuse at the output module whose bit has a value of "1".
- When a GOT is bus-connected to the main base unit or extension base unit, check the connection
status of the extension cable and the grounding status of the GOT.
A01 MULTI CPU ERROR 2001
Details
- During operation, a module was mounted on the slot where the empty setting of the CPU module
was made.
Remedy
- During operation, do not mount a module on the slot where the empty setting of the CPU module
was made.
A01 MULTI CPU ERROR 2011
Details
- The QA*B,QA1S*B was used as the base unit.
Remedy
- Do not use the QA*B,QA1S*B as the base unit.
A01 MULTI CPU ERROR 2100
Details
- In the I/O assignment setting of PLC parameter, intelligent function module was allocated to an I/O
module or vice versa.
- In the I/O assignment setting of PLC parameter, a module other than CPU (or nothing) was allocated
to the location of a CPU module or vice versa.
- In the I/O assignment setting of the PLC parameter, general switch setting was made to the module
that has no general switch setting.
- In the I/O assignment setting of the PLC parameter dialog box, the number of points assigned to the
intelligent function module is less than the number of points of the mounted module.
Remedy
- Make the PLC parameter I/O assignment setting again so it is consistent with the actual status of the
intelligent function module and the CPU module.
- Delete the switch setting in the I/O assignment setting of the PLC parameter.
C70 Setup Manual
Appendix 2.11 Multi CPU Errors (A)
495