A01 MULTI CPU ERROR 3302
Details
- The intelligent function module's refresh parameter is abnormal.
Remedy
- Check the parameter setting.
A01 MULTI CPU ERROR 3303
Details
- In a multiple CPU system, the automatic refresh setting or other parameter setting was made to the
intelligent function module under control of another station.
Remedy
- Delete the automatic refresh setting or other parameter setting of the intelligent function module
under control of another CPU.
- Change the setting to the automatic refresh setting or other parameter setting of the intelligent
function module under control of the host CPU.
A01 MULTI CPU ERROR 3400
Details
- The head I/O number of the target module in the remote password file is set to other than 0H to
0FF0H.
Remedy
- Change the head I/O number of the target module to within the 0H to 0FF0H range.
A01 MULTI CPU ERROR 3401
Details
Position specified as the head I/O number of the remote password file is incorrect due to one of the
following reasons:
- Module is not loaded.
- Other than a the intelligent function module (I/O, A, QnA module)
- Intelligent function module other than the Q series serial communication module, modem interface
module or Ethernet module
- Q series serial communication module or Ethernet module of function version A
The intelligent function module that allows the remote password setting is not mounted.
Remedy
- Mount the intelligent function module (QJ71C24(CMO) or QJ71E71, with version B or later), which
allows the remote password setting, in the position specified in the head I/O No. of the remote
password file.
Details
The Q series serial communication module, modem interface module or Ethernet module of function
version B or later controlled by another CPU was specified in a multiple CPU system.
Remedy
- Change it for the Ethernet module of function version B or later connected by the host CPU.
- Delete the remote password setting.
A01 MULTI CPU ERROR 4000
Details
- The program contains an instruction code that cannot be decoded.
- An unusable instruction is included in the program.
Remedy
- Read the common information of the error using a peripheral device, check error step corresponding
to its numerical value (program error location), and correct the problem.
A01 MULTI CPU ERROR 4002
Details
- The exclusive instruction designated by the program has an incorrect instruction name.
- The exclusive instruction specified in the program cannot be executed by the specified module.
Remedy
- Read the common information of the error using a peripheral device, check error step corresponding
to its numerical value (program error location), and correct the problem.