Appendix 1 Explanation of Parameters

Appendix 1.8 FL-net Parameters

The parameters with "(PR)" requires the CNC to be turned OFF after the settings. Turn the power OFF and ON to enable
the parameter settings.
【#29001(PR)】 IP Address FL-net module IP address
Set the IP address of the FL-net module.
Input a dot-delimited IP address.
Input a node number in the 4th digit.
The standard setting is "192.168.250.1".
---Setting range---
1st digit: 192 to 223
2nd digit: 0 to 255
3rd digit: 0 to 255
4th digit: 1 to 254
【#29002(PR)】 FL-net Unit Mode FL-net module operation mode
Set the FL-net module operation mode.
The standard setting is "0".
0: Online (Communicates with other nodes)
1: Offline (Disconnects the local node from the network.)
2: Loopback test
3: Hardware test
【#29003(PR)】 Node Name Local node name
Set the local node name.
Setting "0" clears the character string currently set.
---Setting range---
9 or less alphanumeric characters
0: Clear
【#29004(PR)】 Cyclic Data Area1 Addr. Cyclic data area 1: Head address
Set the offset from the head device in cyclic data area 1 (bit area) used by the local node.
The standard setting is "0".
---Setting range---
0000 to 01FF
【#29005(PR)】 Cyclic Data Area1 Size Cyclic data area 1: Size
Set the size of cyclic data area 1 (bit area) used by the local node.
The standard setting is "0".
---Setting range---
0000 to 0200
【#29006(PR)】 Cyclic Data Area2 Addr. Cyclic data area 2: Head address
Set the offset from the head device in cyclic data area 2 (bit area) used by the local node.
The standard setting is "0".
---Setting range---
0000 to 1FFF
【#29007(PR)】 Cyclic Data Area2 Size Cyclic data area 2: Size
Set the size of cyclic data area 2 (word area) used by the local node.
The standard setting is "0".
---Setting range---
0000 to 2000
342