Mitsubishi Electric MELSEC iQ-R Series User Manual page 140

C controller/c intelligent function module secs/gem communication software pre-installed model
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Operating procedure
1.
Configure "Setting Request" and "Start Register" in the "IP Address Setting By PLC" screen.
2.
The IP address information is configured by the ladder program as shown below.
Storage destination register
0 to +3
+4 to +7
+8 to +11
3.
Configure the setting trigger.
The SECS/GEM communication software switches OFF the setting trigger.
The file necessary to change the IP address on the SECS/GEM communication software pre-installed model module is
created by the SECS/GEM communication software.
4.
Reset the SECS/GEM communication software pre-installed model module.
After resetting, the IP address of the SECS/GEM communication software pre-installed model module is changed.
Precautions
• For software versions for which default gateway can be set, refer to the following:
(Page 299 Added and Changed Functions)
• CH2 cannot be set for RD55UP06-V-BZ11, RD55UP06-V-BZ13, and RD55UP06-V-BZ15 because they have only one
Ethernet port.
• Do not configure the same IP address between the storage destination register of CH1 and the storage destination register
of CH2.
• When configuring an invalid IP address for a storage destination register, the IP address of a SECS/GEM communication
software pre-installed model module cannot be changed. The value of the storage destination register is changed to that of
the current IP address.
• If changing an IP address fails, an event log will be registered in the event history. Check the event history and
troubleshooting by symptoms and then take corrective actions. (Page 271 Troubleshooting by Symptom)
IP address information
The IP address, subnet mask, and default gateway are configured by four words each.
When the SECS/GEM communication software starts, the IP address information currently configured for the SECS/GEM
communication software pre-installed model module is stored in the IP address information.
The following section shows a configuration sample.
Register
+0W
(IP address)
+4W
(Subnet mask)
+8W
(Default gateway)
7 BASIC FUNCTIONS
138
7.13 IP Address Setting
Description
+0W
+1W
192
168
255
255
0
0
Description
IP Address
Subnet Mask
Default gateway
+2W
3
255
0
+3W
3
0
0