750-940 EnOcean RS-485 Gateway; 868 MHz
DIN-rail mounting is also possible when the Gateway is closed.
As an alternative, the EnOcean Gateway can be completely prepared before
mounting and then mounted to a DIN-rail when closed.
5.4

Connection as a Repeater in an EnOcean Network

The EnOcean Gateway is connected to the external power supply. Once the
power supply has been properly connected, commissioning is complete.
Figure 17: Connection as EnOcean Repeater
To connect the EnOcean Gateway as a repeater, proceed as follows:
1.
To open the EnOcean Gateway, disengage the enclosure cover by turning
gently to the right.
2.
Mount a conductor for the external power supply to the 2-pole, 2-wire
modular PCB connector.
3.
Plug the modular PCB connector to the 2-pole male header on the printed
circuit board.
4.
Use the DIP switches to set the parameters for the EnOcean Gateway for
repeater mode; see Section "Operation Elements."
5.
Connect the other end of the power supply line to the external power supply
source.
6.
Optional: Connect an external antenna to the module SMA socket; see
Section "Installing the External Antenna."
7.
Snap the bottom of the enclosure onto a DIN-rail or mount it on a flat,
stable weight-beating surface; see Section "View."
When using the internal antenna of the EnOcean Gateway, be sure the
mounting surface is non-conductive to avoid negatively influencing the
antenna performance.
8.
Attach the mounted cable to the strain relief.