NOTE: By default, AOUT1 on the main 3PC board follows primary level
14.11

Configuring Digital Outputs

Digital outputs can be sourced from a wide variety of events occurring in the MultiSmart. They can be used
to activate external alarms, control pumps, send signals to SCADA systems and connect to other external
logic (PLCs, relays, etc).
NOTE: Some digital outputs will already be in use as part of the initial configuration. D01 to D03 may
already be configured to control pumps and DO4 will be configured as an alarm output. Any output can
be reconfigured.
Digital outputs are configured from the I/O, Faults & Level screen.
Page 114 of 201
MultiSmart Installation & Operation Manual
Analog Outputs
Assigned
***TopB oard AIN 1
Unassign
Configure Analog Outputs
Inputs
Top Boar d AIN 1
Top Boar d AIN 2
Curren t Level
VFD Curr ent Spee d
Remote S ource
PgUp
PgDn
Select
Config
Input
Select
Advanced
MultiSmart_IO_Manual_A4_v2-22_R15.doc

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MultiSmart and is the answer not in the manual?

Questions and answers

Tommy R Gardner
March 3, 2025

I have four pumps connected to my multi smart. One jockey and three that rotate with the jockey as needed. My problem is that the jockey pump always shows its running even when it isn't running. the other pumps show actuate run times and starts. only the main pump shows continuous run even when it is turned off. I was wondering if there any advice I could be given to resolve this issue.

1 comments:
Mr. Anderson
March 3, 2025

The MultiTrode MultiSmart may show the jockey pump as continuously running even when it is turned off due to the "External Run" status. This occurs if the pump is started by an external control method, such as a manual override switch, where the contactor remains closed but no run command was sent by the controller. As a result, the system continues updating run time statistics and generating relevant faults or warnings. Checking for an external control signal or a stuck contactor may help resolve the issue.

This answer is automatically generated

Table of Contents

Save PDF