12.4.3
Activation & Deactivation delays for level alarms
Each of the four level alarms have an activation delay (5s default) and a deactivation delay (10s default).
High-High Level
High Level
Low Level
Low-Low Level
NOTE: Activation delays can be used to stagger equipment starts from a common level point.
Deactivation delays allow you to pump beyond the normal deactivation level for a set period of time.
NOTE: Activation delays can be used to prevent false alarm trips due to splashing or foam build-up, so
an alarm will only be raised if the level is above the alarm level for a certain time period. Deactivation
delays allow you to be sure the alarm condition has passed before clearing the alarm.
NOTE: The Pump Station Manager can be set up so that it periodically runs past the normal deactivation
level for a configured time, to enable a full well clean-out. This is the well clean out mode in Station
Optimization.