Configuring Digital Outputs

Digital outputs can be sourced from a wide variety of events occurring in the MultiSmart. They can be used
to activate external alarms, control pumps, reverse pumps, send signals to SCADA systems and connect to
other external logic (PLCs, relays, etc).
NOTE: Some digital outputs will already be in use as part of the initial configuration. D01 to D03 may
already be configured to control pumps and DO4 will be configured as an alarm output. All outputs can
be reconfigured.
Digital outputs are configured from the I/O, Faults & Level screen.
Figure 126 – Digital Outputs Screen
Output
TopBoard Dout 05
Sources
All Pumps Available
Pump 2 Off
Operator
OR
Back
Figure 127 – Configure Digital Outputs Screen
Multiple sources can be selected for a digital output. The operations, AND, OR & XOR can be performed on
the multiple sources before the digital output is set. Choose the first source, press Select and then select the
second source; the operator selection box then appears.
MultiSmart_IO_Manual_R20
Configure Digital Outputs
Inputs
All Pumps Availab le
Any Pumps Una vai lable
All Pumps Un available
Any Pumps Fau lted
Pump 1 Off
Pump 2 Off
Pump 3 Off
Pump 1 Off or Unavailabl e
Pump 2 Off or Unavailabl e
Pump 3 Off or Unavailabl e
Any Pumps O ff
All Pumps Off
Advanced
Cancel
Input
Select
Save