13.3.1
Maximum Groups Running
Maximum Groups Running can be used to control the number of groups running when there is more than
one group (default is 1, i.e. only pumps in the same group can run).
For example, for an installation containing jockey pumps and flood pumps it is usual to ensure the jockey
pumps are never running at the same time as the flood pumps. To achieve this, go to Maximum Groups
Running, enable Block running pumps and set the Quantity to 1.
These settings turns off group 1 (the jockey pumps) whenever group 2 starts (the flood pumps). This means
the jockey pumps will never run at the same time as the flood pumps.
13.3.2
Pump Logic in Multi-well Mode
In the case of independent wells, the two wells simply operate as two independent entities with the pumps
allocated to a particular well operating dependant on the level in that well.
In the case of hydraulically connected wells, the pump control module is more complex. If alternation is
enabled (the default), each pump in turn will start regardless of which well it is in, based on the highest level
in either well. Deactivation of a pump is dependant on the level in the well where the pump is located. This
is to prevent problems with equalization between the two wells allowing a well to run dry while a pump is still
operating.
13.4 Decommissioning Pumps
Individual pumps can be decommissioned. This prevents the pump from running under any circumstances,
and also displays a "Decommissioned" notice under the pump on the main operator display.
decommission a pump, navigate to the Commission/Decommission Pumps screen:
Pump Current
Pump 1 Commissioned
Pump 2 Commissioned
Pump 3 Commissioned
Note:
The system will be rebooted to make your changes.
You might want to turn off all pumps before going
through this process.
Figure 97 - Decommissioning Pumps
Select the pump to be decommissioned using the arrow buttons.
•
Press the Decommission button.
•
Page 86 of 201
MultiSmart Installation & Operation Manual
New
Commissioned
Commissioned
Commissioned
MultiSmart_IO_Manual_A4_v2-22_R15.doc
To
Need help?
Do you have a question about the MultiSmart and is the answer not in the manual?
Questions and answers
I have four pumps connected to my multi smart. One jockey and three that rotate with the jockey as needed. My problem is that the jockey pump always shows its running even when it isn't running. the other pumps show actuate run times and starts. only the main pump shows continuous run even when it is turned off. I was wondering if there any advice I could be given to resolve this issue.
The MultiTrode MultiSmart may show the jockey pump as continuously running even when it is turned off due to the "External Run" status. This occurs if the pump is started by an external control method, such as a manual override switch, where the contactor remains closed but no run command was sent by the controller. As a result, the system continues updating run time statistics and generating relevant faults or warnings. Checking for an external control signal or a stuck contactor may help resolve the issue.