14.8.1
Options Available for Special Applications
MultiSmart supports a relative offset around a datum point which can be set through the control panel. In the
Level Devices section mentioned above, an offset around a particular datum point can be specified - this
value is to be added to the MultiSmart level input. These scaled set points can be verified using the DNP or
MODBUS points list.
14.8.2
Probe Configuration
Once the Sensors button is pressed, the digital inputs assigned to the probe are listed. By pressing Config
Sensor these inputs can be assign or unassign as required to match the probe wiring. (The default is Din 2
to Din 11, with Din 1 being 100%).
If necessary more than one probe can be configured for a system, e.g. for 2 wells, or probe in primary and
backup configuration.
Length of Probe (m)
Sensor
1
2
3
4
5
6
7
8
9
Back
Figure 107 – Probe configuration
In a typical system where only one probe is used, the 2
NOTE:
When a 2
connected.
Press the Config Sensor button to make changes to the Digital Input assigned or to the % value that each
sensor indicates. By default, each sensor represents 10% level change. By selecting the model number, the
length of the probe can also be defined.
Page 100 of 201
MultiSmart Installation & Operation Manual
Probe Configuration
100.00
Input
TopBoard DIN 02
TopBoard DIN 03
TopBoard DIN 04
TopBoard DIN 05
TopBoard DIN 06
TopBoard DIN 07
TopBoard DIN 08
TopBoard DIN 09
TopBoard DIN 10
Unassign
Cancel
nd
probe is defined, it is important to assign the Digital Inputs to which this 2
Input
Config
Sensor
Save
nd
probe is not assigned.
MultiSmart_IO_Manual_A4_v2-22_R15.doc
nd
probe is
Need help?
Do you have a question about the MultiSmart and is the answer not in the manual?
Questions and answers
I have four pumps connected to my multi smart. One jockey and three that rotate with the jockey as needed. My problem is that the jockey pump always shows its running even when it isn't running. the other pumps show actuate run times and starts. only the main pump shows continuous run even when it is turned off. I was wondering if there any advice I could be given to resolve this issue.
The MultiTrode MultiSmart may show the jockey pump as continuously running even when it is turned off due to the "External Run" status. This occurs if the pump is started by an external control method, such as a manual override switch, where the contactor remains closed but no run command was sent by the controller. As a result, the system continues updating run time statistics and generating relevant faults or warnings. Checking for an external control signal or a stuck contactor may help resolve the issue.
This answer is automatically generated