6.4

Network Operation Settings

The IP address of the CC-Link IE Controller Network module is set to communicate data with Ethernet devices over
CC-Link IE Controller Network.
GX Works2 is required for the network operation settings. GX Developer cannot be used for setting.
1.
Set network setting parameters. (
2.
Open the setting window in GX Works2.
Project window
3.
Set parameters in the window.
Item
The IP addresses of the control station and submaster station are set
to communicate data with Ethernet devices over CC-Link IE Controller
Network. (
Only the network address part (first and second octets) of the IP
address needs to be set. The network number part (third octet) and
the station number part (fourth octet) are automatically set.
Set IP address
Network address
0 to 255 (0 to FF
(Default: No setting)
• Set an IP address for the control station only.
• Use the same network address for the request source device,
request destination device and modules among them.
• Since automatically assigned, an IP address needs not to be set for
normal stations. (The network address same as that of the control
station is automatically set.)
Page 180, Section 6.2)
[Parameter]
[Network Parameter]
button
Description
Page 108, Section 4.3.2)
1
2
Station No. (automatically set)
1 to 120
)
H
Network No. (automatically set)
1 to 239 (1
to EF
)
H
H
CHAPTER 6 PARAMETER SETTING
[Ethernet/CC IE/MELSECNET]
Setting range
Refer to the descriptions to left.
6
203