Mitsubishi Electric MELSEC Q Series Reference Manual page 380

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Device
Item
(S2)+3
Clear mode
(c) Response data (all set by the user)
When "all stations or a group (FF
will be stored.
Device
Item
(D1)+0
Request type
(D1)+1
Sub-request type
● Remote RUN/STOP is available when the RUN/STOP switch of the target station CPU is set to "RUN".
● Remote RUN/STOP is not executable when system protect is applied to the target station CPU.
● When the target station CPU has been already in remote STOP/PAUSE state by a request from another station, it cannot
enter RUN mode if Mode ((S2+2) is "No forced execution (0001
● If the target station CPU, for which remote STOP was performed, is reset, the remote STOP information is erased.
378
Setting data
Specify the CPU module device status for the case of remote RUN.
0000
: Do not clear
H
(Note that the local devices are cleared.)
0001
: Clear (excluding the latch range)
H
0002
: Clear (including the latch range)
H
Clear mode ((S2)+3) allows specification of the CPU module device
clear (initialization) process at the start of CPU module operation
activated by remote RUN.
After the CPU module clears device data, it enters the RUN status
according to the setting of "Device Initial Value" in the "PLC File" tab
of the PLC parameter in the programming tool.
or 81
to A0
H
H
Setting data
0090
: When station No. is specified in (S1)+5
H
0001
: Remote RUN
H
0002
: Remote STOP
H
)" is specified in Target station No. ((S1)+5), no response data
H
)".
H
Remote
Remote
RUN
STOP
: Set —: Not set
Remote
Remote
RUN
STOP
: Stored —: Not stored