Mitsubishi Electric MELSEC Q Series Reference Manual page 479

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(2) Control data
Device
Item
(S1)+0
(S1)+1
Completion status
Modification
(S1)+2
specification
(S1)+3
Own station No.
(S1)+4 to
(S1)+9
*1
The setting side is as shown below.
User: Before execution of the link dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the link dedicated instruction.
The UINI instruction can be executed only once.
Once a station No. has been set up, the UINI instruction cannot be executed again. (Doing so will result in error completion.)
In the case of error completion of the UINI instruction, take corrective actions against the error and execute the UINI
instruction again.
Remark
Modules are initialized by executing the UINI instruction.
Therefore, cable disconnection is detected in adjacent stations. This may increase IN-side cable disconnection detection
counts (SW0074) or OUT-side cable disconnection detection counts (SW0084).
(3) Function
(a) UINI instruction overview
This instruction sets the station No. of the normal station (own station) that is specified in Un.
Upon completion of the station No. setting, Completion device (D1) turns ON.
Setting data
Unused
The instruction completion status is stored.
0: Normal
Other than 0: Error (
Specify the modification.
0001
: Station No. setting
H
Specify a station No. of the own station.
Unused
[Own station]
CPU module
(S1)
CHAPTER 9 DEDICATED INSTRUCTIONS
Page 511, Section 10.2)
CC-Link IE Controller
Network module
Station No.
UINI
(SW0042)
255
2
Setting
Setting range
*1
side
0
User
System
0001
User
H
1 to 120
User
0
User
477