Appendix 4 Comparison Between Cc-Link Ie Controller Network And Melsecnet/H; Appendix 4.1 Comparison Of Specifications - Mitsubishi Electric MELSEC Q Series Reference Manual

Cc-link ie controller network
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

Appendix 4
This section describes the comparison of specifications between the CC-Link IE Controller Network and the
MELSECNET/H, precautions for system replacement, and precautions for program replacement.
Replace the system according to the description of this section.
Appendix 4.1
The following describes the comparison of specifications between the CC-Link IE Controller Network and the
MELSECNET/H.
(1) Comparison of performance specifications
The transmission of the CC-Link IE Controller Network is made by the optical loop system only.
When the coaxial bus system is used in the MELSECNET/H, consider to replace it with an optical loop system.
The following shows the comparison of optical loop systems in the CC-Link IE Controller Network and the
MELSECNET/H.
Item
LB
Maximum
link points
LW
per network
LX
LY
LB
Maximum
link points
LW
per station
LX
LY
Transient transmission capacity
Communication speed
Number of stations per network
connection cable
Overall cable distance
612
Comparison Between CC-Link IE Controller
Network and MELSECNET/H
Comparison of specifications
CC-Link IE Controller Network
32K points (32768 points, 4K bytes)
(16K points (16384 points, 2K bytes) for Basic
model QCPU or safety CPU)
128K points (131072 points, 256K bytes)
(16K points (16384 points, 32K bytes) for Basic
model QCPU or safety CPU)
8K points (8192 points, 1K byte)
8K points (8192 points, 1K byte)
16K points (16384 points, 2K bytes)
Extended Mode: 32K points (32768 points, 4K
bytes)
16K points (16384 points, 32K bytes)
Extended Mode: 128K points (131072 points,
256K bytes)
8K points (8192 points, 1K byte)
8K points (8192 points, 1K byte)
Max. 1920 bytes
1Gbps
• When Universal model QCPU is used for
control station: 120 (Control station: 1, Normal
station: 119)
• When other than Universal model QCPUs is
used for control station: 64 (Control station: 1,
Normal station: 63)
Optical fiber cable (Multimode fiber)
(
Page 38, Section 2.2.1)
Optical fiber cables used for MELSECNET/H
cannot be used.
66000m (When connecting 120 stations)
MELSECNET/H
16K points (16384 points, 2K bytes)
16K points (16384 points, 32K bytes)
• For MELSECNET/H or MELSECNET/10 mode,
{(LY + LB)  8 + (2 × LW)}  2000 bytes
• For MELSECNET/H extension mode,
{(LY + LB)  8 + (2 × LW)}  35840 bytes
25Mbps/10Mbps
64 stations (Control station: 1, normal station: 63)
Optical fiber cable
30000m

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71gp21-sxMelsec qj71gp21s-sx

Table of Contents