Chapter 6 Configuration; Network Configuration Settings - Mitsubishi Electric AnyWire ASLINK User Manual

Programmable controller
Table of Contents

Advertisement

6
CONFIGURATION
6.1

Network Configuration Settings

Before setting the NZ2AW1GNAL parameters, write the network parameters to the CPU module of the master station.
Also when changing the network configuration, change the network parameters and write them to the CPU module.
For details on how to set the master station, refer to the following.
User's manual for the master station used
If the number of remote I/O signal points and remote register points are set to be less than that in the
NZ2AW1GNAL, no error will occur and the data for the number of points set from the beginning will be
transmitted by cyclic transmission.
The items of the NZ2AW1GNAL set by the engineering tool are as follows.
Item
Station address
Station type
RX/RY setting (points)
RWw/RWr setting (points)
6 CONFIGURATION
40
6.1 Network Configuration Settings
Description
Set the station number of the NZ2AW1GNAL.
Set "Remote Station".
Set "32" + input or output value of "Bit data points setting".
Set "32"+ input or output value of "Word data points setting".