(d) Cyclic transmission restart of own station
1.
Turn Link startup (own station) (SB0000) ON.
2.
When the CC-Link IE Controller Network module accepts the request, Cyclic transmission start
accept status (own station) (SB004C) is turned ON.
3.
When the cyclic transmission restart is completed, Cyclic transmission start completion status
(own station) (SB004D) is turned ON.
4.
If the cyclic transmission restart is completed abnormally, an error code will be stored in Data
linking start status (own station) (SW004D).
5.
Turn Link startup (own station) (SB0000) OFF.
No.
SB0000
Link startup (own station)
SB0001
Link stop (own station)
Cyclic transmission start accept status (own
SB004C
station)
Cyclic transmission start completion status
SB004D
(own station)
Cyclic transmission stop accept status (own
SB004E
station)
Cyclic transmission stop completion status
SB004F
(own station)
308
Description
No.
SW004D
Data linking start status (own station)
SW004F
Data linking stop status (own station)
Description